![AIC N 150 WH Скачать руководство пользователя страница 56](http://html1.mh-extra.com/html/aic/n-150-wh/n-150-wh_installation-and-maintenance-manual_2870755056.webp)
Fig. 18. Draining the Boiler - Typical
I-56
F-084392_EN • B
M
aintenance
Shutting Down for Maintenance
Conditions:
None
Procedure:
1.
Press the On/Off switch located on the right
side of the control panel.
When in the OFF position, the switch
internal light comes out.
2.
To completely cut the power supply to the
boiler, either disconnect the power supply
cable from the boiler, or use the external cir-
cuit breaker.
Follow-on tasks:
i
Restarting after Maintenance
Conditions:
Procedure:
1.
Press the On/Off switch located on the right
side of the control panel.
The switch is illuminated when in ON
position.
2.
Select the required heating mode as re-
quired.
3.
Activate the DHW mode as required.
4.
Allow the appliance to operate for a few min-
utes, then bleed the air from the system.
Follow-on tasks:
1.
Check there is no leak in the water and gas
circuits.
2.
Check the combustion values according to
“Combustion and Gas Data” on page
G-15
.
3.
Record values in
“Combustion Parameters
- Log Sheet” on page I-81
.
4.
Check the heating circuit pressure (between
1.5 and 6 bar).
i
Draining the Boiler
Conditions:
Procedure:
1. Close the isolating valves (
).
2. Connect the optional draining valve (
) to
the sewer with a hose.
3. Open the draining valve (
) to empty the
heating circuit of the boiler.
4. Provide relief at the manual air vent of the boiler.
5. Close the draining valve (
) once the heat-
ing circuit of the boiler is empty.
Follow-on tasks:
None
OFF