ommissioning
Functions
Heating zone 1
720 - Heating curve slope (1.50)
721 - Heating curve displacement (0°C)
730 - Summer-winter heating limit (18°C)
732 - 24-hour heating limit (-3°C)
740 - Flow temp setpoint min (8°C)
741 - Flow temp setpoint max (80°C)
750 - Room influence (
unused
(0%) to 100%)
760 - Room temp limitation (1.0°C)
Domestic Hot Water
1612 - Reduced setpoint (40°C)
1620 - Release (
24h/day
/ Time programs HCs / Time program 4/DHW)
1630 - Charging priority (Absolute / Shifting / None /
MC shifting, PC absolute
)
1640 - Legionella function (Off / Periodically /
Fixed weekday
)
1645 - Legionella function setpoint (65°C)
1641 - Legionella function periodically (3)
1642 - Legionella function weekday (Monday / Tuesday / Wednesday.../ Sunday)
Consumer circuit 1
Consumer circuit 2
Swimming pool circuit
Solar
Skip
Skip
Redo
Redo
Continue
Continue
These sections allow to define the flow temp for different con
-
figurations.
Follow the instructions on the screen if you need to
change anything or skip this chapter. Please contact AIC’s techni
-
cal support for additional information.
i
System setup
LPB system
6600 - Device address (
1
....16)
6601 - Segment address (
0
...14)
6640 - Clock mode (
Autonomously
/ Slave without remote setting / Slave with remote
setting / Master)
Modbus
6651 - Slave address (
unused
(0) ... 247)
6652 - Baud rate (19 200)
6653 - Parity (Even)
6654 - Stop bit (
1
/ 2)