![AIC N 150 WH Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/aic/n-150-wh/n-150-wh_installation-and-maintenance-manual_2870755016.webp)
G-16
F-084392_EN • B
T
echnical
S
pecificaTionS
Hydraulic Data
N 150 WH
water content
l
28.3
pressure drop at ∆T = 20k
mbar
120.0
minimum operating pressure
bar
0.6
maximum operating pressure
bar
6
maximum boiler temperature
°C
85
Pressure Drop Curve
Flow Rate
N 150 WH
minimum water flow rate at ∆T = 20k
l/min
86
nominal water flow rate at ∆T = 20k
l/min
98
00
20
40
60
80
100
120
140
160
200
0
10
20
30
40
50
60
70
80
90
100
110
120
Pressure drop [mbar]
water flow rate [l/min]
hydraulic pressure drop for the N 150 WH
130
140