2  Product description  

  General information  

In the product design, the manufacturer has 

considered the environmental and disposal-

friendliness of the device, in particular, for the 

refrigerant propane (R-290) and the propellant 

pentane (for the insulating foam). Propane does not 

have any ozone depletion potential (ODP) and only a 

very low Global Warming Potential (GWP) of 3.

 

  Technical data 

Important technical data can be found on the serial 

plate (see 

 chapter 2.2.1). 

  External 

dimension 

  Maximum tota  

weight unit

 

 

See 

→ 

Model-Types 

overview

 

Airborne noise 

emissions 

Emission sound pressure 

level < 70 dB(A) 

 

Application/Operating mode 

Setting   

Customer specific 

A1 

 

Customer specific 

A2 

Refrigerator 

A3 

Freezer 

A4 

Ice cream freezer 

A5 

Technical interfaces  

Power supply 

AC 110-120V / 1PH/ 60 Hz 

 

Connector types

 

 

NEMA L5-15  

NEMA 5-15  

Power cord

 or 

IEC-box with plugged-in cables 

(see 

 chapter 7.1) 

Unit – 

connection cables

 

 

Labeling flag with 

snowflake  

Light- 
connection cables 

Labeling flag with  

lamp  

combined Unit/Light- 

connection cables 

No labeling flag   

Minimum requirement

 

for power cords

 

Minimum cross-section 

18AWG 

cabling 

3-pin cable 

 

Electrical protection

 (see 

 chapter 7.2)

 

Fuses

 

Rated 

current

 

[A] 

Triggering 

characteri

stics 

Type 

Fault 

current 

 [mA] 

for 

110-120V

 

CB 

15 

(time-lag)

 

 

GFCI 

 40 

Surge current 

strength, 

short-time 

delayed 

(e.g. G/AP-R)

 

30 

 RCBO  

15 

(time-lag)

 

Surge current 

strength, 

short-time 

delayed 

(e.g. G/AP-R) 

30 

Customized deviations possible. 

Further information: Maintenance services (see 

 

chapter 10.4).  

 

  Serial plate and serial number

 

When handling the unit, the information on the serial 

plate must be observed. The serial plate is located on 

the back side of the unit and contains important 

technical data: 

  Model, 

  Serial number (see 

 chapter 10.4)

  Recommended operating ambient 

temperature* (see 

 chapter 1.3)

  Nominal voltage /frequency, 

  Nominal consumption  

  Nominal current,   

  Refrigerant and quantity, 

  Date of production, 

  Certification marks, 

  Further technical data 

*These units are designed to meet ANSI/ NSF

®

 

Standard #7 requirements in air conditioned stores, 

where temperature is maintained at or below the 

specified levels and relative humidity is maintained at or 

below 55%. Proper installation is required to maintain 

certification.  

Levels specified at 

serial plate  

Recommended operating 

ambient temperature 

Type I (75°F/24°C) 

Between 16°C (61°F) and 

24°C (75°F) 

Type II (80°F/27°C) 

Between 16°C (61°F) and 

27°C (80°F) 

 

  Intended purpose   

For storing, displaying or dispensing of pre-packed ice 

cream, pre-packed frozen or medium temperature  

foods depending on setting (setting see 

→chapter 

2.2).  

Further information see 

 chapter 1.3

 

 

3  Layout and function 

The equipment is a self contained plug-in unit.  

All individual units are delivered ready for operation 

and have their own control unit. 

All units are delivered with a customer specific factory 

setting. Each unit contains one or more hermetically 

sealed refrigerant circuits, the components of which 

are technically connected to each other permanently. 

The units can operate in 5 different operating modes 

(see 

 chapter 4.2.1.2)

  Two settings „Customer specific“,  

  Refrigerator, 

  Freezer or  

  Ice cream freezer. 

The waste heat generated in the unit is discharged to 

the ambient air via an air condenser. 

 

The unit is defrosting automatically to keep the inner 

tank free of frost and ice. The unit works properly 

even when the frost/ice accumulates on the surface 

of the inner tank. Automatic defrost and the button 

[MAN. DEFROST] 

for semi-automatic defrost are set 

inactive in freezer mode. 

Содержание IBIZA 100 NAM

Страница 1: ... Systems GmbH 08 10 2019 16 37 OPERATING MANUAL IBIZA MALTA MANHATTAN MIAMI PARIS SYDNEY Multi mode commercial refrigeration equipment Copyright AHT Cooling Systems GmbH All Rights Reserved SNr 406054 Status 10 19 ...

Страница 2: ...60 353 250 NAM 2 502 x 854 x 833 98 50 x 33 62 x 32 80 180 397 PARIS 145 NAM 1 457 x 853 x 833 57 36 x 33 58 x 32 80 110 243 185 NAM 1 854 x 853 x 833 72 99 x 33 58 x 32 80 140 309 210 NAM 2 102 x 853 x 833 82 76 x 33 58 x 32 80 160 353 250 NAM 2 502 x 853 x 833 98 50 x 33 58 x 32 80 175 386 SYDNEY 175 NAM 1 752 x 993 x 910 69 98 x 39 09 x 35 83 180 397 213 NAM 2 132 x 993 x 860 83 94 x 39 09 x 33...

Страница 3: ...splay elements 11 Temperature display 11 Operating panel and display elements 11 Electronic controller AHT SECOP 11 Switch refrigeration function on off 11 Setting selection 11 Semi automatic defrost 12 Alarm indication and acknowledgment 12 5 Transport and storage 12 6 Unpacking 12 7 Setup and installation 13 Electrical connection 14 Electrical protection 14 8 Commissioning 15 9 Operation use 15 ...

Страница 4: ...epts no liability for damage to persons or things devices goods etc resulting from Non observance of the manual and the regulations safety instructions contained therein Failure to comply with the local safety regulations Inappropriate use misuse Use of unauthorized and non trained staff Unauthorized equipment conversions and technical modifications by the operator himself Use of non approved spar...

Страница 5: ...lk or stand here Light connection cable Do not bore Do not obstruct Intended purpose For storing displaying or dispensing of pre packed ice cream pre packed frozen or medium temperature foods depending on setting see chapter 2 2 and 2 3 The operator is responsible for the correct operation of the unit Operate the unit in a stable position horizontal alignment Operate the unit only on the installed...

Страница 6: ... are recognized by the operating staff and appropriate measures are taken see chapters 9 3 and 10 3 Operating staff The operating staff must be trained by the operator on the transferred tasks and possible dangers with the aid of this manual Only trained operating staff are allowed to operate and clean the device Qualified staff Only AHT authorized qualified staff and specialists are allowed to pe...

Страница 7: ...mmable refrigerant Safety and warning notes for units with flammable refrigerants WARNING The refrigerant R 290 belongs to safety group A3 according to ASHRAE 34 The refrigerant used and the fill quantity are indicated on the power rating plate see chapter 2 2 1 The refrigerant is highly flammable If leaks occur the refrigerant can escape and create an explosive gas air mixture This can lead to fi...

Страница 8: ...ntal and disposal friendliness of AHT units The refrigerant R 290 and the propellant pentane for the insulating foam do not have any ozone depletion potential and do not contribute directly to the greenhouse effect Mechanical hazards WARNING Transport the unit with forklift trucks Risk of injury to persons during collisions Observe the transport routes for forklift trucks Secure the cargo Forklift...

Страница 9: ...act the maintenance service immediately see chapter 10 4 Do not climb onto or into the unit It is prohibited to store glass containers when operating below 0 C 32 F Check breakage of glass containers when operating above 0 C 32 F Disposal of broken glass Cutting injuries to hands Wear protective gloves to remove splintered glass parts and the possibly damaged goods Remove all splintered glass part...

Страница 10: ...ed on the back side of the unit and contains important technical data Model Serial number see chapter 10 4 Recommended operating ambient temperature see chapter 1 3 Nominal voltage frequency Nominal consumption Nominal current Refrigerant and quantity Date of production Certification marks Further technical data These units are designed to meet ANSI NSF Standard 7 requirements in air conditioned s...

Страница 11: ...er 4 2 1 Indoor temperature check Responsibility operating staff Frequency several times a day Operating panel and display elements To get to the operating panel remove the protection acrylic cover with a screwdriver CAUTION Removal of the protection acrylic cover with a screwdriver Stab injury Carefully handling with tool Select the proper size of the screwdriver to avoid slipping After use ensur...

Страница 12: ...ING Damage to refrigerant circuit The refrigerant can escape and create an explosive gas air mixture Risk of fire Do not expose the device during storage and transport to temperatures higher than 70 C 158 F Ensure good ventilation Observe the safety and warning signs for devices with flammable refrigerants see chapter 1 6 2 1 If the unit is damaged contact the maintenance service see chapter 10 4 ...

Страница 13: ...ble final installation position has been reached If you have questions contact the maintenance service see chapter 10 4 Do not climb onto or into the device WARNING If the refrigerant circuit is damaged the refrigerant can escape and create an explosive gas air mixture Risk of fire Do not close the air vents in the unit housing Use only original accessories The unit must only be installed in well ...

Страница 14: ...r and the subsequent damage caused thereby Material and property damage due to a wrong electrical connection Load shedding circuits or device shutdowns are not permitted Unit connection cable At the end of the unit connection cable you can find a labeling flag with a snowflake Fig 4 Symbol snowflake The unit connection cable is used for cooling purposes NOTICE Property damage due to missing connec...

Страница 15: ...may cause electric shock Risk of fire due to sparks or overloading The refrigerant can escape and create an explosive gas air mixture Risk of fire If the unit is damaged or if the electrical protection was triggered 1 Disconnect the unit 2 Secure the unit against restarting 3 Contact the maintenance service see chapter 10 4 Observe the safety and warning signs for units with flammable refrigerants...

Страница 16: ...efore starting work 1 Disconnect the unit 2 Secure the unit against restarting Reasons for decommissioning by qualified staff Maintenance service repair see chapter 10 2 by operating staff Damage to the unit e g broken glass lids Decommissioning The decommissioning must only be performed by trained operating staff or qualified staff WARNING Decommissioning of the unit Contact with live parts may c...

Страница 17: ...sure cleaners Contact with live parts may cause electric shock The refrigerant can escape and create an explosive gas air mixture Risk of fire due to sparks or overloading For basic cleaning do not use steam and high pressure cleaners see chapters 1 6 1 and 1 6 2 1 CAUTION Cutting injuries in the case of material breakage Danger of falling Do not climb onto or into the unit during cleaning Safety ...

Страница 18: ... cloth observe warning notice see chapter 10 5 b Units with defrost water plug Place a pan under the drain Remove the defrost water plug Let the defrost water drain off Close the drain with the defrost water plug again Fig 8 Unit with view on defrost water plug 6 Remove food residues such as spilled liquids and packaging residues 7 Clean the interior of the unit Clean the defrost drain Remove and ...

Страница 19: ...ices For questions regarding maintenance service repair etc please contact your regionally competent AHT service partner AHT service line See sticker on the unit Email product_support aht at Online contact www aht at services QR Code The maintenance services have access to all necessary and current information for commissioning and maintenance e g spare parts lists 11 Disposal WARNING Escaping ref...

Страница 20: ...sgasse 57 Austria Tel 43 3614 2451 0 Fax 43 3614 2451 8 Email office aht at Internet www aht at AHT Cooling Systems Brasil Ltda Rua Onório Bortolato 1065 Bairro Pedreiras Navegantes SC 88375 000 Brasil Phone 55 0 11 4702 30 99 Fax 55 0 11 4702 71 68 Email info br aht at AHT Cooling Systems Changshu Co Ltd 215500 Changshu 88 Yangguang Avenue Jiangsu Province P R China Phone 86 512 5236 7100 Fax 86 ...

Отзывы: