14
6) If the incoming water line to the heater is equipped
with a check valve, water meter, or pressure-reduc-
ing valve, an expansion tank must be installed in
the system. This will prevent weeping from the
water heater relief valve and premature failure of
the heater due to expansion of the water during the
heating cycle.
7) Before acquisition of a water heater for space heat-
ing application, it is necessary to have the area of
intended use sized by a qualified technician.This
will ensure that an adequate water heating
capacity will be available for both heating and
potable water supply, and that the application will
meet all local codes and public utility requirements.
Note:
It is good practice to oversize the water heater,
to ensure that all of the potential hot water
requirements are available.
Blower Unit
M
High Limit Switch
Vacuum Switch (N.O.)
Y
ello
w
Red
Power Cord
White
Black
Green
Black
White
Blue
Yellow
Red
Yellow
Blue
Hot Surface Igniter
Flame Sensor
Gas Control
White
Black
Green
5
3
4
1
6
2
5
3
4
1
6
2
5
3
4
1 2
Y
ello
w
5
3
4
1 2
W
hit
e
G
ree
n
B
ro
w
n
B
ro
w
n
Capacitor
B
ro
w
n
Green
Flammable Vapor Sensor
Unité de Ventilation
M
Interrupteur Haute
Limite
Interrupteur de Pression
Négative (N.O.)
Jau
ne
Rouge
Cordon d'Alimentation
Blanc
Noir
Vert
Noir
Blanc
Bleu
Jaune
Rouge
Jaune
Bleu
Allumeur à Élément
Chauffant
Détecteur de Flamme
Contrôle au gaz
Blanc
Noir
Vert
5
3
4
1
6
2
5
3
4
1
6
2
5
3
4
1 2
Ja
un
e
5
3
4
1 2
B
lan
c
V
ert
B
ru
n
B
ru
n
Condensateur
B
ru
n
Vert
Détecteur de Vapeur Inflammable
Pour le manuel IM061 UG75PV2
Figure 13
Wiring Diagram
Wiring
This water heater uses an external electrical source
for power. It must be electrically grounded in accor-
dance with all local codes or, in the absence of local
codes, CSA C22.1 Canadian Electrical Code, in
Canada, and/or the National Electrical Code, ANSI/
NFPA 70, in the United States. Failure to properly
ground this water heater can result in property dam-
age, personal injury, or death.
DANGER
WARNING
CAUTION
AVERTISSEMENT
ATTENTION
Before lighting your water heater, check that all of the
wires have been installed correctly (
see Figure 13
).
Make sure that none of the wires are grounded, have
split, or are broken. Verify that all wiring connections
are properly secured, as there is a possibility that
they have become loose during transport. If any of
the original wiring needs replacing, use only
18AWG-type, or greater wire that is approved for
221
o
F (105
o
C).
INSTALLATION INSTRUCTIONS