54
while power is off, the outlet pressure of the valve will
not be adjusted and will remain the same and will be
re-assigned to the new wheel selection.
6. Repeat steps 4 and 5 if necessary.
7. Once low fire manifold pressure has been adjusted,
slide the gas valve ON/OFF switch to the OFF posi-
tion. Allow the indoor blower to complete off delay.
8. Disconnect electrical power to furnace. Remove
blower door.
9. Remove jumper across R and W1 to remove heat call.
10. Re-connect thermostat wires. There should be no call
for heat present at the thermostat.
11. Turn gas manual shut-off valve located outside the
furnace to the CLOSED position.
12. Remove manifold pressure tap. Replace and tighten
manifold tap plug.
13. Slide gas valve ON/OFF switch to the ON position.
14. Turn gas manual shut-off valve to the OPEN position.
Check for gas leaks using an approved leak detector.
Do NOT use a flame of any kind to check for leaks.
Repair any leaks before continuing with furnace ad-
justments.
STEP 3: VERIFy THE INPUT RATE
Once the orifices have been selected and the manifold
pressure set, the input rate of the furnace can be deter-
mined by clocking the amount of time it takes for your
meter to make one revolution. Table 16 specifies the num-
ber of cubic feet per hour based on the number of sec-
onds measured for one revolution of the meter (meters
listed are; (a) one cubic meter per revolution and (b) ten
cubic meters per revolution).
Once you have determined the number of cubic feet per
revolution, the input rate of the furnace can then be deter-
mined using the following formula:
Input Rate = ((Gas Rate (ft
3
/ Hour)) x (Altitude-Adjusted
Gas Heating Value (BTU’s/ft
3
))
Note the units which cancel:
Input Rate = (Gas Rate (ft
3
/Hour) x (Altitude-Adjusted Gas
Heating Value (BTU’s/ft
3
))
Example
:
The following information is determined:
1. Altitude-Adjusted Gas Heating Value = 975 BTU/ft
3
(given from gas supplier)
2. Meter used is 1 revolution per ft
3
3. Time per revolution at high fire = 36 seconds (this is
measured by the installer).
4. The formula for Gas Rate is as follows:
Gas Rate (ft
3
/hr) with 1ft
3
/Rev Meter = (3600)/(Revolu-
tion Time (in seconds))
Gas Rate (ft
3
/hr) with 1ft
3
/Rev Meter = (3600)/(36 Sec-
onds)
Gas Rate = 100 ft
3
/Hour
(Note this value could have also been taken directly
from Table 15).
Input Rate = ((Gas Rate (ft
3
/ Hour)) x (Altitude-Adjusted
Gas Heating Value (BTU’s/ft
3
))
Fill in the values:
Input Rate = ((100ft
3
/Hour) x (975 BTU’s/ft
3
)
Input Rate = 97,500 BTU’s/Hour
If the rate calculated does not match the furnace input on
the rating label (below 2,000 ft) or the elevation-corrected
rate calculated in item of above (
Selecting the Orifices
)
(at or above 2,000 ft in elevation) /-5%, the next
larger orifice (if rate is too low) or the next smaller orifice
(if the rate is too high) must be installed and the process
repeated from (Adjusting the Gas Pressures).
Repeat steps 2 and 3 until the proper rate is achieved
with the manifold pressure within the tolerances spec-
ified herein.
When both of these adjustments are correct,
proceed to Step 4,
Adjusting Gas Heat Temperature
Rise
.
To determine the gas flow rate, calculate the cubic ft per
hour use the following formulas or use the following table:
Gas Rate (ft
3
/hr) w 1ft
3
/Rev Meter = (3600)/(Revolution
Time (in seconds))
Gas Rate (ft
3
/hr) w 2ft
3
/Rev Meter = (7200)/(Revolution
Time (in seconds))
Gas Rate (ft
3
/hr) w 5ft
3
/Rev Meter = (18000)/(Revolution
Time (in seconds))
FURNACE ADJUSTMENTS
Fu
rn
ac
e
Ad
ju
stm
en
ts
Содержание (-)98VA060M317USA
Страница 12: ...Field Conversions FIELD CONVERSIONS 12 ...
Страница 13: ...FIELD CONVERSIONS Field Conversions 13 SEE NExT PAGE FOR APPLICABLE CONFIGURATIONS ...
Страница 15: ...Field Conversions 15 ...
Страница 16: ...Field Conversions ST A1194 68 00 16 ...
Страница 17: ...Field Conversions 17 ...
Страница 18: ...Field Conversions 18 ...
Страница 43: ...43 CONDENSATE DRAIN CONDENSATE DRAIN DRAIN NEUTRALIzER cont Condensate Drain FIGURE 29 ST A1194 70 00 ...
Страница 86: ...86 Timing Diagram TIMING DIAGRAM TABLE 16 TIMING DIAGRAM FOR A CALIBRATION GAS HEAT SEqUENCE ST A1240 03 00 ...
Страница 87: ...87 TIMING DIAGRAM TABLE 17 TIMING DIAGRAM FOR NON CALIBRATION GAS HEAT SEqUENCE Timing Diagram ST A1240 04 00 ...
Страница 92: ...92 Diagnostics TABLE 19 R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Страница 93: ...93 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Страница 94: ...94 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Страница 95: ...95 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Страница 96: ...96 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Страница 97: ...97 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Страница 98: ...98 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Страница 99: ...99 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Страница 100: ...100 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Страница 101: ...101 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Страница 105: ...105 FIGURE 67 MODULATING ECM FURNACE WIRING DIAGRAM Troubleshooting ...
Страница 106: ...106 ...
Страница 107: ...107 ...
Страница 108: ...108 CM 0717 ...