Vent terminations for both Non-Direct and Direct-Vent in-
stallations must adhere to guidelines specified by the lat-
est edition of ANSI Z21.47
Gas-Fired Central Furnaces
.
These are clearly detailed in
Figure 26
for Direct-Vent in-
stallations. In addition to these requirements, the installa-
tion and venting must also comply with the National Fuel
Gas Code (U.S.) and CSA-B149.1; Canadian Natural Gas
and Propane Installation Code (Canada) and the following
requirements must also be met:
NOTE:
Screens of any kind on the inlet or exhaust pipes
are not permitted and will void the manufacturer’s war-
ranty.
In addition to the requirements shown in
Figure 26
for Di-
rect-Venting, the vent must be installed with the following
minimum clearances:
1. The vent terminal shall have a minimum horizontal
clearance of 4 feet from electric meters, gas meters,
regulators and relief equipment.
2. Locate the furnace combustion air inlet a minimum of 3
feet from the vent of any other gas or fuel-burning ap-
pliance or clothes dryer to prevent recirculation of the
flue gases into the furnace combustion air inlet. The
only exception to this requirement is the case of multi-
venting two or more furnaces, which is covered in the
section on multiventing of these instructions.
In addition to the minimum clearances listed above and in
Figure 26
(Direct-Vent), the vent location should also be
governed by the following guidelines.
1. Avoid terminating under any kind of patio or deck. How-
ever, if necessary, vent piping may be installed under a
deck as long as the termination(s) is (are) not under
the deck.
2. If installing the vent under a deck, insulate it to insure
that no condensate freezes and blocks the pipes.
3. Do not terminate in any area or behind any obstruction
that may allow the flue products to become stagnant
and/or re-circulate.
4. Do not locate on the side of a building with prevailing
winter winds. This will help prevent moisture from
freezing on the walls and overhangs (under eaves).
5. If extending vent through a brick or masonry surface, a
sleeve between the wall and venting is suggested to
protect against damage from thermal expansion and
contraction.
6. A corrosion-resistant sheet metal or plastic backing
plate installed on the wall behind the vent is suggested
to prevent exhaust gases and condensate from con-
tacting the wall.
7. Avoid locating too close to shrubs as condensate may
stunt growth or kill them.
TERMINATION REqUIREMENTS
!
CAUTION
THE COMBUSTION PRODUCTS AND MOISTURE
IN THE FLUE GASES WILL CONDENSE AS THEy
LEAVE THE TERMINATION. THE CONDENSATE
CAN FREEzE ON THE ExTERIOR WALL, UNDER
THE EAVES AND ON SURROUNDING OBJECTS.
SOME DISCOLORATION TO THE ExTERIOR OF
THE BUILDING IS TO BE ExPECTED. HOWEVER,
IMPROPER LOCATION OR INSTALLATION CAN
RESULT IN FINISH DAMAGE TO THE BUILDING
AND MAy RE-CIRCULATE THE PRODUCTS OF
COMBUSTION INTO THE COMBUSTION AIR TER-
MINAL AND FREEzE.
GENERAL VENTING REqUIREMENTS AND
GUIDELINES
Ve
nt
in
g
Содержание (-)98VA060M317USA
Страница 12: ...Field Conversions FIELD CONVERSIONS 12 ...
Страница 13: ...FIELD CONVERSIONS Field Conversions 13 SEE NExT PAGE FOR APPLICABLE CONFIGURATIONS ...
Страница 15: ...Field Conversions 15 ...
Страница 16: ...Field Conversions ST A1194 68 00 16 ...
Страница 17: ...Field Conversions 17 ...
Страница 18: ...Field Conversions 18 ...
Страница 43: ...43 CONDENSATE DRAIN CONDENSATE DRAIN DRAIN NEUTRALIzER cont Condensate Drain FIGURE 29 ST A1194 70 00 ...
Страница 86: ...86 Timing Diagram TIMING DIAGRAM TABLE 16 TIMING DIAGRAM FOR A CALIBRATION GAS HEAT SEqUENCE ST A1240 03 00 ...
Страница 87: ...87 TIMING DIAGRAM TABLE 17 TIMING DIAGRAM FOR NON CALIBRATION GAS HEAT SEqUENCE Timing Diagram ST A1240 04 00 ...
Страница 92: ...92 Diagnostics TABLE 19 R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Страница 93: ...93 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Страница 94: ...94 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Страница 95: ...95 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Страница 96: ...96 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Страница 97: ...97 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Страница 98: ...98 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Страница 99: ...99 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Страница 100: ...100 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Страница 101: ...101 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Страница 105: ...105 FIGURE 67 MODULATING ECM FURNACE WIRING DIAGRAM Troubleshooting ...
Страница 106: ...106 ...
Страница 107: ...107 ...
Страница 108: ...108 CM 0717 ...