![AHRI (-)98VA060M317USA Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/ahri/98va060m317usa/98va060m317usa_installation-instructions-manual_2870554009.webp)
9
1.
IMPORTANT:
If installing the unit over a finished ceil-
ing or living area, be certain to install an auxiliary con-
densate drain pan under the entire unit. This auxiliary
drain pan should extend under any evaporator coil in-
stalled with the furnace and the open portion of the
condensate drain assembly. See “Condensate
Drain/Neutralizer” section for more details.
2.
IMPORTANT:
If using a cooling evaporator coil with
this furnace, be sure the air passes over the heat ex-
changer before passing over the cooling coil. The
cooled air passing over the warm ambient air inside
the heat exchanger tubes can cause condensation in-
side the tubes resulting in corrosion and eventual fail-
ure.
If these are manual dampers, they must be equipped to
prevent heating or cooling operation unless the damper is
in the full heat or cool position.
3.
IMPORTANT:
Furnace must be installed level from
front-to-back or with a slight tilt such that the back of
the furnace is up to 1/2” higher than the front of the
furnace as shown in Figure 3.
NOTE:
These furnaces are approved for installation in at-
tics, as well as alcoves, utility rooms, closets and crawl-
spaces. Provisions must be made to prevent freezing of
condensate.
FREEzE PROTECTION
For installations where the furnace may reach tempera-
tures below 32°F (0°C) (such as an alcove or attic installa-
tion), the installer must take precautions to ensure that the
drain trap and connected drain pipe do not freeze. Local
codes and practices should be followed in order to prevent
freezing.
If the drain trap is installed within the furnace cabinet, no
freeze protection is required. When the trap is mounted
outside or partially outside the cabinet, it must be pro-
tected from freezing. Regardless of the location of the
drain trap, any exposed drain piping must be protected
from freezing as required by local practices or codes. A UL
or CSA listed heat tape or UL or CSA approved heating
cable with a rating of 3-6 watts per foot is acceptable pro-
tection when installed and maintained in accordance with
the manufacturer’s instructions. Good installation practices
necessitate that the installer verify heat tape operation in
accordance with the manufacturer’s instructions at the
time of installation.
IMPORTANT:
Support this unit when installed. Since this
furnace is suitable for attic or crawl space installation, it
may be installed on combustible wood flooring or by using
support brackets as required.
SITE SELECTION
1. Select a site in the building near the center of the pro-
posed, or existing, duct system.
2. Give consideration to the vent system piping when se-
lecting the furnace location. Be sure the venting sys-
tem can get from the furnace to the termination with
minimal length and elbows.
3. Locate the furnace near the existing gas piping. Or, if
running a new gas line, locate the furnace to minimize
the length and elbows in the gas piping.
4. Locate the furnace to maintain proper clearance to
combustibles as shown in following Figure 5.
FIGURE 3
1/4" MIN. TO 1/2" MAX. TILT
TOWARD THE FRONT
OF THE CABINET IN ALL
INSTALLATIONS AND
ORIENTATIONS
UPFLOW / DOWNFLOW
ST-A1194-13-X0
LOCATION REqUIREMENTS
GENERAL INFORMATION
Lo
ca
tio
n
!
WARNING
WHEN THIS FURNACE IS INSTALLED IN A RESI-
DENTIAL GARAGE, IT MUST BE INSTALLED SO
THE BURNERS AND IGNITION SOURCE ARE LO-
CATED NO LESS THAN 18 INCHES [450MM] ABOVE
THE FLOOR. THIS IS TO PREVENT THE RISk OF IG-
NITING FLAMMABLE VAPORS WHICH MAy BE
PRESENT IN A GARAGE. ALSO, THE FURNACE
MUST BE LOCATED OR PROTECTED TO AVOID
PHySICAL DAMAGE By VEHICLES. FAILURE TO
FOLLOW THESE WARNINGS CAN CAUSE A FIRE
OR ExPLOSION, RESULTING IN PROPERTy DAM-
AGE, PERSONAL INJURy OR DEATH.
0-1/2
(
HIGHER
THAN FRONT
OF FURNACE
BACK
FRONT
UPFLOW
!
WARNING
THIS FURNACE IS NOT APPROVED OR RECOM-
MENDED FOR INSTALLATION ON ITS BACk, WITH
ACCESS DOORS FACING UPWARDS.
Содержание (-)98VA060M317USA
Страница 12: ...Field Conversions FIELD CONVERSIONS 12 ...
Страница 13: ...FIELD CONVERSIONS Field Conversions 13 SEE NExT PAGE FOR APPLICABLE CONFIGURATIONS ...
Страница 15: ...Field Conversions 15 ...
Страница 16: ...Field Conversions ST A1194 68 00 16 ...
Страница 17: ...Field Conversions 17 ...
Страница 18: ...Field Conversions 18 ...
Страница 43: ...43 CONDENSATE DRAIN CONDENSATE DRAIN DRAIN NEUTRALIzER cont Condensate Drain FIGURE 29 ST A1194 70 00 ...
Страница 86: ...86 Timing Diagram TIMING DIAGRAM TABLE 16 TIMING DIAGRAM FOR A CALIBRATION GAS HEAT SEqUENCE ST A1240 03 00 ...
Страница 87: ...87 TIMING DIAGRAM TABLE 17 TIMING DIAGRAM FOR NON CALIBRATION GAS HEAT SEqUENCE Timing Diagram ST A1240 04 00 ...
Страница 92: ...92 Diagnostics TABLE 19 R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Страница 93: ...93 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Страница 94: ...94 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Страница 95: ...95 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Страница 96: ...96 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Страница 97: ...97 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Страница 98: ...98 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Страница 99: ...99 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Страница 100: ...100 Diagnostics TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS ...
Страница 101: ...101 TABLE 19 continued R98V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics ...
Страница 105: ...105 FIGURE 67 MODULATING ECM FURNACE WIRING DIAGRAM Troubleshooting ...
Страница 106: ...106 ...
Страница 107: ...107 ...
Страница 108: ...108 CM 0717 ...