![Agilent Technologies E1330B Скачать руководство пользователя страница 71](http://html.mh-extra.com/html/agilent-technologies/e1330b/e1330b_users-manual-and-scpi-programming-manual_2867439071.webp)
Agilent E1330B Digital I/O Module Command Reference
69
Chapter 5
:VME:ADDRess
MEMory:VME:ADDRess [<
base
>]<
address
>
establishes the address of add-on
VME memory in the system which can then be used to store block data in commands
with the
:TRACe
keyword.
Parameters
Comments
•
base specifies the numeric format as decimal, hexadecimal, octal, or binary.
IEEE-488.2 specifies the following values for this parameter:
Decimal = no parameter
Hexadecimal = #H
Octal = #Q
Binary = #B
•
Valid values for base and address are #H200000 (2,097,152 decimal) through
#HDFFFF8 (14,680,056 decimal).
•
For this memory to actually be used it must also have a defined length and
have been turned ON using the
MEMory:VME:STATe
command.
•
Related Commands:
[SOURce:]DIGital:TRACe:DEFine
,
MEMory:VME:ADDress?
,
MEMory:VME:SIZE
,
MEMory:VME:STATe
•
*RST Condition: #H200000
Example
MEM:VME:ADDR #H200000
sets the starting VME address to 200000
16
.
:VME:ADDRess?
MEMory:VME:ADDRess? [<MIN|MAX>]
queries for the current VME memory
address. The optional parameter lets you query for the fixed minimum or maximum
address.
Parameters
Comments
•
This command always returns the address in decimal format.
•
The address returned using
MIN
is always
2,097,152
.
•
The address returned using
MAX
is always
14,680,056
.
•
Related Commands:
MEMory:VME:ADDRess
,
MEMory:VME:SIZE?
,
MEMory:VME:STATe?
Parameter Name
Parameter Type
Range of Values
Default
<
base
>
Discrete
none, #H, #Q, or #B
Decimal
<
address
>
Numeric
or
Discrete
200000
16
–DFFFF8
16
MIN or MAX
None
Parameter Name
Parameter Type
Range of Values
Default
MIN|MAX
Discrete
none, MIN, or MAX
None
Содержание E1330B
Страница 2: ......
Страница 10: ...8 Notes ...
Страница 11: ...9 Notes ...
Страница 12: ...10 Notes ...
Страница 25: ...Configuring the Agilent E1330B Digital I O Module 23 Chapter 2 Figure 2 6 J1 and J2 Connector Pinouts ...
Страница 32: ...30 Configuring the Agilent E1330B Digital I O Chapter 2 Notes ...
Страница 42: ...40 Using the Agilent E1330B Digital I O Module Chapter 3 Notes ...
Страница 58: ...56 Understanding the Agilent E1330B Digital I O Module Chapter 4 Notes ...
Страница 104: ...102 Agilent E1330B Digital I O Module Command Reference Chapter 5 Notes ...
Страница 146: ...144 Error Messages Appendix C Notes ...