![Agilent Technologies E1330B Скачать руководство пользователя страница 59](http://html.mh-extra.com/html/agilent-technologies/e1330b/e1330b_users-manual-and-scpi-programming-manual_2867439059.webp)
Agilent E1330B Digital I/O Module Command Reference
57
Chapter 5
Chapter 5
Agilent E1330B Digital I/O Module
Command Reference
Using This Chapter
This chapter describes Standard Commands for Programmable Instrumentation
(SCPI) and summarizes IEEE 488.2 Common (*) Commands applicable to the
Digital I/O Module.
•
Command Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 57
•
SCPI Command Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 60
•
IEEE 488.2 Common Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 98
•
Command Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 99
Command Types
Commands are separated into two types: IEEE 488.2 Common Commands and SCPI
Commands.
Common
Command
Format
The IEEE 488.2 standard defines the Common Commands that perform functions
like reset, self-test, status byte query, etc. Common Commands are four or five
characters in length, always begin with the asterisk character (*), and may include
one or more parameters. The command keyword is separated from the first
parameter by a space character. Some examples of Common Commands are shown
below:
*RST
*ESR 32
*STB?
SCPI
Command
Format
SCPI commands perform functions like closing switches, making measurements,
querying instrument states, or retrieving data. A subsystem command structure is a
hierarchical structure that usually consists of a top level (or root) command, one or
more lower level commands, and their parameters. The following example shows
part of a typical subsystem:
[SOURce:]
DIGital
:DATA
n
[:VALue]?
:BIT
m
?
[SOURce:]
is the root command,
DIGital
is a second level command,
:DATA
n is a
third level command (where n is the port number 0–3), and [
:VALue]
and
:BIT
m are
fourth level commands (where m is the queried bit location).
Содержание E1330B
Страница 2: ......
Страница 10: ...8 Notes ...
Страница 11: ...9 Notes ...
Страница 12: ...10 Notes ...
Страница 25: ...Configuring the Agilent E1330B Digital I O Module 23 Chapter 2 Figure 2 6 J1 and J2 Connector Pinouts ...
Страница 32: ...30 Configuring the Agilent E1330B Digital I O Chapter 2 Notes ...
Страница 42: ...40 Using the Agilent E1330B Digital I O Module Chapter 3 Notes ...
Страница 58: ...56 Understanding the Agilent E1330B Digital I O Module Chapter 4 Notes ...
Страница 104: ...102 Agilent E1330B Digital I O Module Command Reference Chapter 5 Notes ...
Страница 146: ...144 Error Messages Appendix C Notes ...