AGF Manufacturing Inc. • Phone: 610-240-4900 • Fax: 610-240-4906 • www.testandrain.com
5
Wiring:
The M5400 is protected internally by a 3A circuit breaker and requires
120VAC power source to function. Ensure the breaker in the main panel is
sized appropriately. Refer to the image below that coincides with your model.
Run conduit to the ½” connection on the top of the unit.
1.
Open the door using the supplied keys.
2.
Loosen the four screws on the front of the M5400 Alarm Panel Box and
3.
carefully remove the door.
Run a single set of appropriately sized power wires into the Alarm Panel
4.
(Refer to the electrical schematic as necessary).
NOTE: Use dedicated junction boxes (not provided) to make wire connections
when installing more than one M5400 on a circuit.
Connect the 120VAC Hot Wire to the circuit breaker.
5.
Connect the 120VAC Neutral Wire to one of the neutral terminals.
6.
Connect the ground wire to the green/yellow ground terminal.
7.
The M5400 can be connected to a Remote Panel. This is accomplished through a
set of N.O. (close on alarm) auxiliary contacts.
Run two additional wires into the M5400 Alarm Panel.
1.
Connect one wire to the AC1 (auxiliary contact) Terminal.
2.
Connect the other wire to the AC2 (auxiliary contact) Terminal.
3.
Connect these wires to the appropriate place in the Remote Panel.
4.
Neutral Wire
Ground Wire
Auxiliary Contact
Wires
M5400A
M5400H
Hot Wire
Hot Wire
Neutral Wire
Ground Wire
Auxiliary Contact
Wires