TABLE OF CONTENTS

Installation Instructions ............................................................... 4-7

Unpacking .........................................................................................4
Sprinkler System Preparation ...........................................................4
Mounting ...........................................................................................4
Wiring ................................................................................................5
Verify Correct Operation ............................................................... 6-7

Operating Instructions ................................................................. 7-8

Maintenance Instructions .......................................................... 9-11

Verify Alarm Operation ................................................................ 9-10
Heater Operation ..............................................................................9
Changing Timer Setting ..................................................................10
Changing Thermostat Setting ................................................... 10-11
Maintenance Log ............................................................................11

AGF Manufacturing Inc.

100 Quaker Lane • Malvern, PA 19355

Phone: 610-240-4900 

Fax: 610-240-4906

www.testandrain.com

AGF Manufacturing Inc.

Содержание COLLECTanDRAIN 5400

Страница 1: ...1 Model 5400 Owner s Manual INST 5400A_V001 4 1 15 AGF Manufacturing Inc...

Страница 2: ...eration 6 7 Operating Instructions 7 8 Maintenance Instructions 9 11 Verify Alarm Operation 9 10 Heater Operation 9 Changing Timer Setting 10 Changing Thermostat Setting 10 11 Maintenance Log 11 AGF M...

Страница 3: ...h float switch and alarm for dry pipe sprinkler systems The M5400 is designed for installation in climates where freezing or below freezing temperatures are present and result in the failure of typica...

Страница 4: ...installed Relieve air pressure from the branch line 2 Remove the existing auxiliary drain 3 Mounting Use the four mounting tabs 3 8 holes x 4 to install the M5400A to a wall or other secure structure...

Страница 5: ...as necessary NOTE Use dedicated junction boxes not provided to make wire connections when installing more than one M5400 on a circuit Connect the 120VAC Hot Wire to the circuit breaker 5 Connect the 1...

Страница 6: ...50 F 5 NOTE It is the owner s responsibility to set the thermostat based upon the climate conditions of the installed location The default setting of 50 F is adequate for outside temperatures down to...

Страница 7: ...age Ambient Temperature F Est Daily Power Consumption Rotate the red Thermostat Set Point Dial clockwise until the heater turns on 5 NOTE The alarm will sound about 2 seconds after the heater turns on...

Страница 8: ...has been drained close the Drain Valve 5 lower valve Open the Supply Valve upper valve and allow time for any 6 additional water to accumulate Repeat the process until all of the accumulated water ha...

Страница 9: ...rm Panel for five seconds to 1 verify that the alarm horn sounds and the alarm light pulses MODEL 5400A Verify heater operation CAUTION Always take the necessary precautions when entering the alarm pa...

Страница 10: ...l to the previous setting 7 Install the Alarm Panel Cover and tighten the four screws securely 8 Change Timer Setting M5400H Only NOTE It is the owner s responsibility to set the timer based upon the...

Страница 11: ...________ _________ ________________________________________________ ________ _________ ________________________________________________ ________ _________ ____________________________________________...

Страница 12: ...AGF Manufacturing Inc 100 Quaker Lane Malvern PA 19355 Phone 610 240 4900 Fax 610 240 4906 www testandrain com...