Fig. 12
DESN 517045
GAS ADJUSTMENT FOR
NATURAL GAS/PROPANE
Pressure Testing
The maximum gas inlet pressure to the appliance must not exceed 12” wg for N.G. and 14” for L.P. Gas. The minimum gas
inlet pressure at the appliance must not be less than 5” w.g. Natural Gas and 11” wg L.P. Gas to enable the correct manifold
pressure to be obtained.
NOTE:
The regulator is pre-set for either N.G. or L.P. Gas.
Use the small hotplate burner injector as the pressure test point.
For Natural Gas manifold pressure is 4” w.g.
For L.P.G. (Propane Only) manifold pressure 10” w.g.
19