Seperator alarm WGA 01 D • Manual
Afriso EMA AB, Kilvägen 2, SE-232 37 Arlöv • Tel: +46-40-92 20 50 • Fax +46-40-19 33 58 • [email protected] • www.afriso.se
Troubleshooting
Note:
If an input did not have a sensor
installed when the system was
installed, this will not be scanned.
To activate an inactive output, see
the Maintenance section.
Note:
Sensors are activated in a
sequence: Sensor 1 (level sen-
sor WGA-ES4 ) active in 4 sec
-> sensor 2 (thermistor sensor
WGA-R6-S) active in 45 sec ->
sensor 3 (sludge sensor WGA-
ES8) active in 4 sec.This se-
quence is repeated continuously.
Checks when alarms appear in the display
Problem
Check
Cause/action
Layer alarm
Damming alarm
Sludge alarm
“Level alarm act.” alarm appears
in the display
“Sensor err on input 1 (level)” alarm
appears in the display
“Sensor err on input 2 (high level)”
alarm appears in the display
“Sensor err on input 3 (sludge)”
alarm appears in the display
“Sludge alarm act.” alarm
The sludge level has reached a set
alarm level (normal alarm)
“High level alarm act.” alarm
Check the thickness of the oil/grease
layer
Measure voltage at sensor
Measure voltage at sensor
Measure voltage at sensor
Blockage at outlet to separator
(critical alarm)
This normally means that the sludge
layer in the tank is too great, this
normally results in impairment of the
efficiency of the separator. Separator
emptying should be ordered.
Order emptying
Error in sensor circuit to sensor (e.g.
cable failure/short-circuit)
Error in sensor circuit to sensor (e.g.
cable failure/short-circuit)
Error in sensor circuit to sensor (e.g.
cable failure/short-circuit)
Clear blockage or find out cause