Aerovent IM-895 Скачать руководство пользователя страница 5

Installation, Operation & Maintenance Manual

IM-895

5

Follow proper handling instructions as given earlier.

1.  Installation of piping must be in accordance with local 

codes and ANSI Z223.1-latest edition, "National Fuel Gas 

Codes" (in Canada CAN/CGA-B149 Code).

2.  Piping to the unit must conform to local and national 

requirements for type and volume of gas handled, and 

pressure drop allowed in the line. Refer to the unit rating 

plate to determine the BTU capacity of the unit and 

the type of gas the unit is designed to use. Using this 

information, refer to the ASHRAE Guide Fundamentals 

Handbook, or other gas pipe sizing guides, to determine 

the correct supply pipe size. Allow sufficient pipe size 

based on allowable pressure drop in supply line. Where 

several units are served by the same main, the total 

capacity of all the units served by the main must be used. 

Do not use pipe sizes smaller than 1/2".

3.  Pipe size to the unit must match the factory side access 

gas connection size, 1" NPT.

4.  Install a ground joint union with brass seat and a manual 

shut-off valve external to the unit casing, as shown in 

Figure 7.1, adjacent to the unit for emergency shut-off 

and easy servicing of controls. Include a 1/8" NPT plugged 

tapping accessible for test gauge connections.

5.  Provide a sediment trap, as shown in Figure 7.1, before 

each unit and where low spots in the pipeline cannot be 

avoided.

6.  This unit requires a constant minimum gas supply pressure, 

6.5" w.c., when the unit is operating at maximum gas flow. 

If the gas supply pressure exceeds 1 psig, a gas pressure 

regulator must be installed before the unit to prevent 

damage to the internal valve components. If the pressure 

is lower than 6.5" w.c., the heater may not perform to 

specifications.

7.  Support piping so that no strains are imposed on the unit 

controls when connected.

Unit Installation

 (Gas Connections)

1.  All field gas supply lines should be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equivalent 

for testing.

2.  Gas pressure to the unit controls must never exceed the pressure shown on the unit rating plate. The unit and its individual shutoff valve(s) 

must be disconnected from the gas supply during any test pressure more than 0.5 psig (3.5 kPa).

3.  For test pressure less than 0.5 psig (3.5 kPa), the unit gas control must be isolated from the supply gas piping by closing the unit manual 

shutoff valve(s).

4.  For an indoor unit, where required by Code, use a dedicated line for venting gas to the outside of the building.

WARNING

1.  Purging of air from gas supply lines should be performed 

as described in ANSI Z223.1-latest edition “National Fuel Gas 

Code” or in Canada in Can/CGA-B149 codes.

2.  Do not operate unit with a gas input rate greater than that 

shown on the unit rating plate.

3.  A Model ADH cannot substitute for make-up air. If severe 

negative pressure exists because of exhaust loads, make-up 

air must be provided for the ADH to operate properly.

CAUTION

8.  Blow out the gas line to remove debris before making 

connections.

9.  Purge the gas line to remove air before attempting to start 

unit. Purging of air from gas lines should be performed as 

described in ANSI Z223.1-latest edition "National Fuel Gas 

Code" or in Canada in CAN/CGA-B149.

10.  All field gas piping must be pressure/leak tested prior 

to unit operation. Use a non-corrosive bubble forming 

solution or equivalent for leak testing. The heater and 

its individual shut-off valve must be disconnected from 

the gas supply piping system during any pressure testing 

of that system at test pressures more than 0.5 psig. The 

heater must be isolated from the gas supply piping system 

by closing its individual manual shutoff valve during any 

pressure testing of the gas supply piping system at test 

pressures equal to or less than 0.5 psig.

11.  Weatherize all utility clearance holes on the unit after 

connections have been made.

Figure 7.1. Required Piping to Unit Gas Controls

 

GAS 

SUPPLY LINE 

 

GROUND 

JOINT 

UNION 

W/ BRASS 

SEAT 

GAS 

SUPPLY LINE 

MANUAL GAS 

SHUT-OFF VALVE 

TO 

CONTROLS 

3 " 

MIN. 

PLUGGED 

1 /8" NPT TEST 

GAGE CONNECTION 

 

SEDIMENT 

TRAP 

Manual gas shut-off valve is in 

the "off" position when handle 

is perpendicular to pipe. 

Содержание IM-895

Страница 1: ...Additional product and engineering information is available at www aerovent com Refer to the Safety section s in this manual prior to installing or servicing the door air heater The most current versi...

Страница 2: ...is isolated by closing off the inlet or outlet to prevent wind driven rotation If an impeller is chocked to prevent rotation ensure that the chocks are removed prior to start up Wear appropriate pers...

Страница 3: ...the unit after acceptance is not the responsibility of Twin City Fan Companies Ltd Unpack each carton or crate and verify for conformance with description of product ordered and all required parts an...

Страница 4: ...g down and attach to the angle rings on the door air heater Make sure the rod locations do not interfere with gas train or electrical control panel access If desired provide one suspension type vibrat...

Страница 5: ...alent for testing 2 Gas pressure to the unit controls must never exceed the pressure shown on the unit rating plate The unit and its individual shutoff valve s must be disconnected from the gas supply...

Страница 6: ...f the process 7 External electrical connections to be installed include Supply power connection 115 208 230 380 460 or 575 volts Connection of thermostats and remote monitoring panels that may be supp...

Страница 7: ...voltage to the voltage required for the unit controls 3 Flame Safeguard Control The flame safeguard control monitors safety devices to determine if the gas ignition sequence should be initiated Once i...

Страница 8: ...re supplied with redundant automatic main gas shut off valves to control gas flow to the modulating gas valve 11 These valves may be a combination gas valve as shown which have two valve seats in one...

Страница 9: ...n of the door air heater Remote monitoring panel features include Fan Switch All panels include a fan On Off switch Burner Switch All panels include a burner On Off switch Temperature Control Discharg...

Страница 10: ...ment or installation Check burner and fan impeller to ensure it is secure Check all electrical connections for tightness Check to ensure there are no obstructions to the inlet air supply or the discha...

Страница 11: ...nect an inclined manometer b If the outdoor air temperature is below 60 F fire the main burner to achieve a discharge air temperature of approximately 70 F If the burner does not fire under these cond...

Страница 12: ...e to make sure the burner lights smoothly and the flame is present across the entire length of the burner 14 With the unit off close the main gas manual hand valve If applicable remove the U tube mano...

Страница 13: ...r temperature does not exceed the maximum allowable limit for safe operation 2 With the safety devices described in the above steps verified the flame safeguard control is enabled to initiate the igni...

Страница 14: ...accumulation of scale or foreign material on either side of the mixing plates should be removed with a wire brush 2 Add fresh di electric grease Grainger p n 23YC40 inside the flame rod boot 3 Check...

Страница 15: ...f the unit and in the gas supply line to the unit 2 Turn off the electric supply to the unit at the unit disconnect Lock the disconnect to prevent tampering 3 Protect outside air openings to prevent t...

Страница 16: ...ot 6 Defective flame rod 6 Check and or replace 7 Defective flame safeguard controller 7 Check and or replace 8 Short in flame sensor leads 8 Check and or replace 9 Excessive air velocity across burne...

Страница 17: ...ice of the unit s to which this applies must be performed by a qualified installation and service agency 3 After completion of start up make a copy of this completed form for your files as necessary a...

Страница 18: ...nect Wiring is over 200 Long Please Consult Factory 2 Gas supply connected with proper gas pressure regulator drip leg etc Yes No 3 Electrical supply connected with proper voltage amperage as stated o...

Страница 19: ...Electrical Service Provided to Unit Volts Phase Hertz Amps 2 Unit Nameplate Electrical Requirements Volts Phase Hertz Amps 3 Main Fusing Size if applicable Volts Amps 4 Overload Relay Setting if appl...

Страница 20: ...but with fan and gas on and unit in forced high fire 7 The Service Pressure with burner in high fire is __________ w c or ________oz or ________psig 8 The High Temperature Limit Switch is field set to...

Страница 21: ...ts IV Miscellaneous Operational Checks 1 With the unit fan and burner operating all of the circuit check lights are illuminated except the burner lock out pilot light and the low temperature switch pi...

Страница 22: ...ussed the unit controls and operation was Name Title please print please print CUSTOMER S AUTHORIZED SIGNATURE I acknowledge that I have been instructed on the operation of this unit Signature Date Ph...

Страница 23: ...Installation Operation Maintenance Manual IM 895 23...

Страница 24: ...WWW AEROVENT COM 5959 Trenton Lane N Minneapolis MN 55442 Phone 763 551 7500 Fax 763 551 7501 2021 Aerovent...

Отзывы: