background image

26

E

nglish

The unit must be connected directly 
to an electrical outlet or to an 
independent circuit. 
To protect the unit against short circu-
its, fit an omnipolar thermal-magnetic 
trip 2A 250V (IG) to the power line 
with a minimum contact opening 
distance of 3mm.

C H A R A C T E R I S T I C S   O F   T H E 
CONNECTION CABLES
Use H05V-K or N07V-K type cables 
with 300/500V with insulation, piped 
or ducted.
All the cables must be piped or ducted 
until they are inside the fan coil.
The cables coming out of the pipe or 
duct must not be subject to stretching 
or twisting. They must be protected from 

external agents.

Stranded wires can only be used with 
terminating sleeves. Make sure that the 
strands of the wires are inserted pro-
perly.
Wiring diagrams are constantly upda-
ted. It is therefore compulsory to refer 
to the ones supplied with the unit.

The control panel may not be fitted on 
a metal wall unless this is permanently 
connected to an earthed outlet.
The control panels consist simply of 
electric circuits connected at the mains 
voltage of 230V; all the inputs for the 
probes and controls must therefore be 
correspondingly insulated for this vol-
tage.
Multifunctional electronic thermostats 

are provided ready for operation in the 
standard configuration but allow the 
installer to adjust them to the specific 
necessities of the system by modifying 
the internal dip-switch configuration.
The functions that can be customised might 
vary from model to model, for this reason it 
is advisable to consult the relevant manuals.

WARNING:check whether the instal-
lation has been carried out correct-
ly. FOLLOW THE CHECKING PROCE-
DURES indicated in the control panel 
manuals.

INSTALLATION

INSTALLING THE UNIT

ELECTRICAL WIRINGS

WARNING: before carrying out any 
intervention, check the power supply is 
disconnected.
WARNING:before carrying out any 
work, put the proper individual 
protection equipment on.
WARNING: the appliance must be fitted 
according to the national regulations on 
process plant engineering.
WA R N I N G :   e l e c t r i c a l   w i r i n g s , 
installation of the fan coils and relevant 
accessories should be performed by 
a technician who has the necessary 
technical and professional expertise 
to install, modify, extend and maintain 
systems, and who is able to check the 

systems for the purposes of safety and 
correct operation. 
WARNING: install a device, main 
switch or plug which allows to 
completely cut off the power supply 
from the unit.

Instructions which are essential for the 
proper installation of the equipment are 
given here.
The completion of all the operations 
in accordance with the specific 
requirements is however left to the 
experience of the installation engineer.
Do not install units in rooms where 
there are inflammable gases or acid 
or alkaline substances that could 

irretrievably damage the aluminium-
copper heat exchanger or the internal 
plastic parts.
Do not install the unit in workshops or 
kitchens where the oil vapours mixed 
with the treated air can be deposited 
on the exchange coils, reducing their 
performance, or on the parts inside the 
unit, damaging the plastic parts.
Choose a position at the centre of the 
room whenever possible; adjusting the 
air output allows air to be distributed 
optimally within the room. 

Do not 

install at a height above three metres.

-  Choose the place where to install 

the unit according to the layout of 
the room, the number of units to be 
installed and any limitations imposed 
by the architecture. Check that the 
chosen place facilitates installing and 
servicing the unit.

-  Install four M8 threaded rods into the 

ceiling to hold the frame.

VEC allows 2 installation options thanks 

to the grill prepared to be fixed in two 
positions:

A) for suspended ceiling installation with 

reduced space that requires units with 
small dimensions.

B) allows (increasing total height) 

to increase the difference in level 
between condensate drain and 
suspended ceiling by a further 30 
mm, to make the realisation of the 
condensate drain ducting even easier, 
in order to prevent, in most cases, 
the necessity for a condensate drain 
pump.

To install the VEC unit, proceed as 

follows:

-  open the cardboard box
-  if necessary, mount any accessory 

before installing the unit on the ceiling 

  WARNING: consult the relevant 

manuals of the accessories

- lift the unit carefully and, keeping it 

slightly inclined, attach it to the 4 
threaded bars using 8 nuts, 4 of which 
are self-locking. Operate the nuts 
to adjust height; finally, check that 
the unit is installed in a horizontal 
position

-  lay the hydraulic pipes through the 

suspended ceiling to the attachment 
plate on the unit

-  make the hydraulic connections as 

described in the relative chapter

-  bring the condensate discharge pipe 

so that it matches the relative fitting on 
the condensate discharge device

-  drain the system via the drain valve
- bring the power supply and the 

control cables close to the electrical 
box 

-  adjust the position of the unit from the 

support bracket by means of the nuts 
so that the unit is level and the frame 
rests slightly on the suspended ceiling

-  start the fan coil unit and carry out 

an operation test; the functions are 
described in the User Manual

Содержание VEC

Страница 1: ...TECHNICAL MANUAL VEC COANDA EFFECT FAN COIL IVECTY 0906 5074502_01 Replace 5074502_00 0904 ...

Страница 2: ......

Страница 3: ...ctions for use accompanied by the words DANGER or WARNING because if they are not complied with the machine property can damaged and or people can be injured If any kind of malfunction is not included in this manual con tact the local After Sales Service immediately The device must be installed in such a way that maintenance and or repair operations are possible The device warranty does not in any...

Страница 4: ...ONVECTEURS série VEC auquel cette déclaration fait référence est conforme aux normes harmonisées suivantes EN 60335 2 40 EN 55014 1 EN 55014 2 EN 61000 6 1 EN 61000 6 3 satisfaisant ainsi aux conditions essentielles des directives suivantes Directive LVD 2006 95 CE Directive compatibilité électromagnétique 2004 108 CE VEC APC PLUS ACCESSOIRES Il est interdit de faire fonctionner l appareil avec de...

Страница 5: ...n wieviele Geräte stapelbar sind Apilamiento observe en el embalaje la posición de la flecha para saber cuántos equipos pueden apilarse NON calpestare Do NOT trample NE PAS marcher sur cet emballage Nicht betreten NO pisar NON trasportare la macchina da soli se il suo peso supera i 35 Kg DO NOT handle the machine alone if its weight is over 35 Kg NE PAS transporter tout seul l appareil si son poid...

Страница 6: ...people or if gas appliances or sources of odours are present ADJUST TEMPERATURE ADEQUATELY The room temperature should be adjusted in order to provide maximum comfort to the people in the room especially if they are elderly children or sick people avoid differences over 7 C between the outdoor temperature and the temperature inside the room in summer Carefully choose the room temperature so as to ...

Страница 7: ...ry VEC 20 VEC 20 GL VEC 30 VEC 30 GL VEC 40 VEC 40 GL VEC 50 VEC 40 GL DESCRIPTION OF THE UNIT VEC 20 VEC 20 GL System types The VEC fan coils are designed for systems with 2 and 4 pipes in the versions without valve with 3 way water valve VCF with 2 way water valve for variable flow rate systems VCFD with electric heater RX with electric heater RX and valve VCF VCFD with hot water coil for system...

Страница 8: ...el to be mounted on the wall Consult the characteristics and compa tibility of the control panels supplied as an accessory Some control panels can control a network of fan coils if they are used in combination with the interface cards SIT3 and SIT5 supplied as accessories The AERMEC fan coil versions without a control panel can all be combined with the HSH AERDOMUS centralised control system using...

Страница 9: ...ling VC Solenoid valve Heating VF Solenoid valve Cooling SA Room temperature sensor V3 V2 V1 Maximum Average or Minimum fan speed RX Electric heater CONFIGURATIONS FOR SYSTEMS WITH VEC System with 2 pipes without water sensor System with 4 pipes with water sensor System with 4 pipes without water sensor Key ...

Страница 10: ...umber of fans Sound pressure Sound power Water contents Max motor power Max input current Max motor power with electric heater Input current with electric heater Coil connections 3R Coil connections 1R Power supply VEC with a 3 row coil VEC 20 VEC 30 VEC 40 VEC 50 W max 1835 2770 3745 4285 W med 1505 2340 3105 3785 W min 1105 1950 2505 2840 W 950 1300 1650 1950 W max 1320 1950 2985 3610 W med 1085...

Страница 11: ...fan is set to its minimum speed level In the event of prolonged fan inactivity and with cold water passing through the coil condensate may form on the exter nal case of the unit As a result we rec ommend including the three way valve accessory OPERATING LIMITS In order to prevent air stratification in the room and therefore to achieve improved mixing it is obligatory not to supply the fan coil wit...

Страница 12: ...1324 7 745 974 1405 1964 549 670 792 907 1070 1242 8 3 737 1054 1497 1987 695 860 1019 1180 1320 1454 4 658 920 1331 1823 2315 613 780 939 1103 1251 1391 5 601 793 1154 1639 2155 568 688 850 1005 1173 1325 6 719 985 1430 1976 528 649 772 918 1081 1251 7 875 1223 1757 488 609 734 846 988 1161 9 3 660 909 1344 1823 625 779 944 1103 1250 1384 4 590 798 1156 1653 2147 547 694 861 1020 1181 1322 5 542 ...

Страница 13: ...1095 1317 1543 1758 8 3 1036 1520 2120 951 1183 1397 1603 1774 1940 4 932 1344 1935 2554 868 1082 1295 1530 1710 1885 5 831 1180 1710 2376 3034 770 977 1203 1425 1639 1817 6 742 1024 1509 2160 2848 689 868 1101 1317 1539 1745 7 893 1315 1915 2644 638 795 982 1212 1435 1663 9 3 919 1301 1908 860 1071 1296 1510 1685 1855 4 840 1165 1687 2337 773 977 1190 1417 1621 1795 5 744 1016 1489 2129 2808 670 ...

Страница 14: ... 1865 2217 2540 2819 3091 4 1446 2091 2968 3971 1366 1701 2058 2405 2714 2994 5 1301 1791 2645 3674 4703 1165 1529 1886 2236 2583 2880 6 1123 1525 2284 3291 4398 1062 1316 1694 2055 2411 2751 7 1333 1927 2895 4053 976 1224 1480 1869 2234 2598 9 3 1443 2040 2934 1372 1689 2038 2392 2675 2951 4 1301 1785 2622 3624 1212 1531 1891 2230 2564 2853 5 1111 1564 2272 3284 4349 1021 1360 1713 2069 2408 2734...

Страница 15: ... 2915 8 3 2184 2909 1808 2118 2410 2678 2978 3263 4 2003 2652 3557 4644 1644 1988 2285 2573 2861 3155 5 1788 2403 3266 4304 5519 1449 1833 2148 2447 2738 3041 6 1565 2150 2923 3927 5157 1182 1637 1996 2306 2600 2904 7 1886 2614 3564 4741 1368 1818 2159 2469 2764 9 3 1981 2592 3467 1630 1974 2259 2535 2822 3112 4 1807 2365 3188 4229 1462 1836 2143 2429 2707 3000 5 1603 2146 2893 3881 5091 1253 1658...

Страница 16: ...Δt C water inlet temperature air inlet temperature Heating capacity kW VEC 40 Δt C water inlet temperature air inlet temperature Heating capacity kW VEC 50 Water flow rate l h Water flow rate l h HEATING CAPACITY CORRECTION FACTORS The heat yields refer to the maximum speed For the rest of the speeds the values must be multiplied by the following factors MOD VEC20 VEC30 VEC40 VEC50 Average speed 0...

Страница 17: ...let temperature air inlet temperature Heating capacity kW VEC 50 BV142 HEATING CAPACITY CORRECTION FACTORS The heat yields refer to the maximum speed For the rest of the speeds the values must be multiplied by the following factors MOD VEC20 VEC30 VEC40 VEC50 Average speed 0 86 0 87 0 90 0 93 Minimum speed 0 69 0 76 0 81 0 80 The heat yield of the 3 row coil in fan coils fitted with the BV coil ac...

Страница 18: ...p when the average water temperature varies Average water temperature C 5 10 15 20 50 60 70 Multiplication coefficient 1 03 1 0 96 0 91 0 78 0 75 0 72 The pressure drops in the previous diagram refer to an average water temperature of 65 C The following table shows the correc tion to apply to the pressure drop when the average water temperature varies Average water temperature C 5 10 15 20 50 60 7...

Страница 19: ...1 1 2 6 7 8 9 10 11 12 13 14 15 16 17 C Average glycol water temperature Correction factor 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 6 7 8 9 10 11 12 13 14 15 16 17 18 C Average glycol water temperature Correction factor 30 40 50 60 70 80 90 C 0 8 0 9 1 0 1 1 1 2 1 3 1 4 Average glycol water temperature Correction factor 0 8 0 9 1 0 1 1 1 2 1 3 1 4 30 40 50 60 70 80 90 C Average glycol water...

Страница 20: ...0 8 36 4 31 24 9 6 5 49 9 42 E Min 29 8 37 33 1 30 2 23 9 20 2 6 6 39 7 35 E Max 40 6 45 8 43 4 39 7 36 28 3 14 7 49 3 45 E VEC30 Med 36 42 38 7 34 7 28 9 23 4 4 44 9 40 E Min 29 9 37 1 33 2 30 23 9 20 2 4 1 39 8 35 E Max 44 1 49 3 46 9 43 2 39 5 31 8 18 2 52 8 48 5 E VEC40 Med 38 6 43 8 41 4 37 7 34 26 3 12 7 47 3 43 E Min 32 9 40 1 36 2 33 26 9 23 2 7 1 42 8 38 E Max 48 6 53 8 51 4 47 7 44 36 3 ...

Страница 21: ...of the electric heater when desired and auto matic summer winter switchover accor ding to water temperature Equipped with a minimum water temperature sen sor that interrupts the heating function when the water temperature is below 35 C By suitably adjusting the dip switches on the card it can also be used for 2 pipe or 4 pipe systems without an electric heater Wall mounting See the accessory instr...

Страница 22: ...ngs and 3 way valves of the all or nothing type that work with a 230V and 24V power supply Available for fan coils with 3 row coil VCFD1 VCFD124 VCFD2 VCFD224 with additional 1 row coil BV VCFD4 VCFD5 ACCESSORIES Consult the compatibility table to make your choice Obligatory VEC accessory 20 30 40 50 VEC20GL VEC30GL VEC40GL FMT10 FMT20AW KTLP PX2 PXAE PXAR WMT05 WMT10 VEC Accessory 20 30 40 50 AMP...

Страница 23: ...sate drain ducting even easier in order to prevent in most cases the necessity for a condensate drain pump In this case it is mandatory to apply the insulating gasket to the filter retainer divider supplied to prevent by pass between intake and flow Moreover after having fixed the frame to the fan coil using the 4 screws apply the insulating tape supplied to the entire exposed perimeter of the fra...

Страница 24: ...g capacity of electric heater W RX 22 RX 32 RX 42 RX 50 950 1300 1650 1950 Electric heater input current A RX 22 RX 32 RX 42 RX 50 4 13 5 65 7 17 8 48 AMP20 SUPPORTS FOR INSTALLATION BV WATER BASED HEATING COIL DSC4 CONDENSATE DISCHARGE DEVICE RX ELECTRIC HEATER VCFD 2 WAY VALVE Flow direction VCF 3 WAY VALVE A B AB IN OUT ...

Страница 25: ...25 English SIT3 SIT5 INTERFACE CARDS V1V2V3 OUTPUT N PH L V2V1 N V3 INPUT 52 65 90 15 DIN SIT 3 SIT 5 ACCESSORIES SW3 MINIMUM WATER TEMPERATURE SENSOR ...

Страница 26: ...proper installation of the equipment are given here The completion of all the operations in accordance with the specific requirements is however left to the experience of the installation engineer Do not install units in rooms where there are inflammable gases or acid or alkaline substances that could irretrievably damage the aluminium copper heat exchanger or the internal plastic parts Do not ins...

Страница 27: ...27 English INSTALLATION H2O H2O AIR H2O A B ...

Страница 28: ...28 English INSTALLING AND REPLACING THE AIR FILTER INSTALLATION Installation A Installation B ...

Страница 29: ...lish DIMENSIONS mm L I Max 3000mm 284 A 314 B 388 43 129 8 216 A 246 B 279 A 309 B 63 5 VEC 20 30 40 50 L mm 540 771 991 991 I mm 440 671 891 891 Weight VEC kg 15 5 20 6 24 7 24 7 Weight VEC GL kg 3 7 5 7 7 7 ...

Страница 30: ...in loco On site wiring Raccordements à effectuer in situ Vor Ort auszuführende Anschlüsse Cableado in situ AR Arancio Orange Orange Orange Naranja BI Bianco White Blanc Weiss Blanco BL Blu Blue Bleu Blau Azul GR Grigio Grey Gris Gray Gris MA Marrone Brown Marron Braun Marrón NE Nero Black Noir Schwarz Negro RO Rosso Red Rouge Rot Rojo VE Verde Green Vert Grün Verde VI Viola Violet Violet Violet Vi...

Страница 31: ...Nos schémas électriques étant constamment mis à jour il faut absolument se référer à ceux fournis à bord de nos appareils Die Schaltpläne werden ständig aktualisiert deswegen muss man sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la m...

Страница 32: ...do macchina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas électriques étant constamment mis à jour il faut absolument se référer à ceux fournis à bord de nos appareils Die Schaltpläne werden ständig aktualisiert deswegen muss man sich stets auf das mit dem Gerät gelieferte Schaltsc...

Страница 33: ...férer à ceux fournis à bord de nos appareils Die Schaltpläne werden ständig aktualisiert deswegen muss man sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma VEC KTLP VCF VEC KTLP VC VF 2 tubi 2 tube 2 tuyaux 2 Röhren 2 tubos 4 tu...

Страница 34: ...r à ceux fournis à bord de nos appareils Die Schaltpläne werden ständig aktualisiert deswegen muss man sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma VEC WMT10 VCF 2 tubi 2 tube 2 tuyaux 2 Röhren 2 tubos VEC WMT10 VF VC 4 tubi...

Страница 35: ...r à ceux fournis à bord de nos appareils Die Schaltpläne werden ständig aktualisiert deswegen muss man sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma VEC FMT10 VCF 2 tubi 2 tube 2 tuyaux 2 Röhren 2 tubos VEC FMT10 VF VC 4 tubi...

Страница 36: ...r à ceux fournis à bord de nos appareils Die Schaltpläne werden ständig aktualisiert deswegen muss man sich stets auf das mit dem Gerät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma VEC FMT20 VCF 2 tubi 2 tube 2 tuyaux 2 Röhren 2 tubos VEC FMT20 VF VC 4 tubi...

Страница 37: ...MS SW SW M1 JP1 EXT INT Gli schemi elettrici sono soggetti ad un continuo aggiornamento è obbligatorio quindi fare riferimento a quelli a bordo macchina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas électriques étant constamment mis à jour il faut absolument se référer à ceux fourn...

Страница 38: ...by the user it involves a series of simple operations thanks to which the fan coil can operate at its maximum efficiency level Before carrying out any work make sure the electricity supply is unplugged Do not remove the shell or the mechanical electrical protection devices Interventions Internal cleaning once a year or before the machine is shut down for a long period In rooms where a high level o...

Страница 39: ...in der Produktion Änderungen und Verbesserungen ohne Ankündigung durch zuführen Los datos técnicos indicados en la presente documentación no son vinculantes Aermec S p A se reserva el derecho de realizar en cualquier momento las modificaciones que estime necesarias para mejorar el producto Aermec partecipa al Programma di Certificazione EUROVENT I prodotti interessati figurano nella Guida EUROVENT...

Отзывы: