12
E
nglish
COOLING CAPACITY
The cooling capacities yielded shown in the table must be multiplied by the following factors:
MOD.
VEC
20
Maximum speed
total power
1.00
sensible power
1.00
Average speed
total power
0.82
sensible power
0.82
Minimum speed
total power
0.61
sensible power
0.59
VEC20
TOTAL COOLING CAPACITY [W]
SENSIBLE COOLING CAPACITY [W]
Water temp. °C
Wet bulb air temperature [°C]
Dry bulb air temperature [°C]
Inlet
t
15
17
19
21
23
21
23
25
27
29
31
5
3
1089
1523
1984
–
–
932
1096
1255
1391
1525
1655
4
977
1390
1839
2299
2783
851
1017
1181
1323
1460
1595
5
834
1207
1666
2147
2643
756
917
1082
1251
1395
1532
6
762
1027
1476
1980
2487
712
836
984
1157
1322
1464
7
–
923
1264
1785
2315
672
794
904
1056
1231
1392
6
3
955
1368
1836
2299
–
858
1019
1183
1322
1459
1587
4
847
1221
1687
2147
2635
766
935
1096
1253
1392
1527
5
737
1054
1497
1987
2487
688
836
1000
1167
1325
1463
6
686
893
1301
1815
2323
649
772
908
1075
1244
1395
7
–
832
1097
1594
2144
611
735
848
979
1150
1321
7
3
834
1207
1666
2147
–
774
933
1104
1253
1390
1519
4
740
1062
1513
1987
2479
685
855
1019
1181
1324
1458
5
660
909
1320
1823
2323
629
760
924
1085
1253
1396
6
622
799
1126
1620
2152
589
712
834
997
1160
1324
7
–
745
974
1405
1964
549
670
792
907
1070
1242
8
3
737
1054
1497
1987
–
695
860
1019
1180
1320
1454
4
658
920
1331
1823
2315
613
780
939
1103
1251
1391
5
601
793
1154
1639
2155
568
688
850
1005
1173
1325
6
–
719
985
1430
1976
528
649
772
918
1081
1251
7
–
–
875
1223
1757
488
609
734
846
988
1161
9
3
660
909
1344
1823
–
625
779
944
1103
1250
1384
4
590
798
1156
1653
2147
547
694
861
1020
1181
1322
5
542
689
1001
1443
1980
508
627
768
928
1094
1255
6
–
649
850
1250
1777
467
589
711
845
1004
1170
7
–
–
782
1054
1551
426
549
670
791
916
1076
10
3
601
793
1154
1639
2155
554
699
863
1018
1179
1317
4
522
700
998
1454
1972
485
622
785
939
1103
1252
5
–
627
860
1261
1793
446
567
691
857
1014
1177
6
–
–
755
1075
1566
406
528
648
774
929
1089
7
–
–
–
926
1357
363
488
609
735
847
1000
11
3
–
688
1001
1443
1980
482
629
781
943
1100
1246
4
–
630
861
1261
1788
425
550
701
863
1021
1180
5
–
568
752
1089
1580
386
507
627
777
934
1096
6
–
–
675
934
1368
344
467
589
711
853
1007
7
–
–
–
821
1170
299
426
549
669
791
926
12
3
–
627
860
1261
1793
409
558
704
865
1017
1175
4
–
561
752
1097
1585
364
485
630
788
941
1102
5
–
–
663
944
1376
324
446
567
699
862
1016
6
–
–
617
808
1188
282
406
528
648
778
936
7
–
–
–
739
1006
233
363
488
609
732
852
13
3
–
568
752
1089
1580
343
487
633
784
943
1096
4
–
–
671
931
1374
303
424
558
708
865
1019
5
–
–
597
810
1188
262
385
506
630
784
936
6
–
–
–
709
1016
215
344
467
587
711
860
7
–
–
–
–
869
158
299
426
549
669
789