18
E
nglish
VEC20
VEC30
VEC40
VEC50
Water flow rate [l/h]
Coil pressure drops [kP
a]
3R COIL PRESSURE DROPS
The pressure drops in the previous diagram refer to an average water temperature of 10°C. The following table shows the correc-
tion to apply to the pressure drop when the average water temperature varies.
Average water temperature °C
5
10
15
20
50
60
70
Multiplication
coefficient
1.03 1 0.96 0.91 0.78 0.75 0.72
The pressure drops in the previous diagram refer to an average water temperature of 65°C. The following table shows the correc-
tion to apply to the pressure drop when the average water temperature varies.
Average water temperature °C
5
10
15
20
50
60
70
Multiplication
coefficient
1.4 1.36 1.31 1.24 1.06 1.02 0.98