![AERMEC NRL Скачать руководство пользователя страница 32](http://html1.mh-extra.com/html/aermec/nrl/nrl_technical-manual-installation-maintenance_2861924032.webp)
FOR THE INSTALLER
19. SELECTION AND PLACE OF
INSTALLATION
Before installing the unit, decide with
the customer the position in which it
will be placed, pay attention to the
following points:
−
The support surface must be able to
withstand the weight of the unit;
−
The safety distance between the
units and other equipment or
structures must be strictly respected
so that the air in fans inlet and outlet
circulates freely.
−
The unit must be installed by an
authorised technician in compliance
with the national laws in the country
of destination respecting the
minimum technical spaces to allow
maintenance.
20. POSITIONING
The machine is delivered from the
factory wrapped in estincoil.
Before moving the unit, check the lifting
capacity of the machines used.
Once the packaging has been
removed, the unit must be handled by
qualified personnel with the suitable
equipment. To handle the machine:
see figure
−
Hook up the lifting belts to the
provided eyebolts (as indicated in
figure).
WARNING: ALWAYS USE ALL THE
PROVIDED EYEBOLTS
−
In order to avoid damaging the unit
with the cables, insert protection
elements between them and the
machine. It is absolutely forbidden
to stand beneath the unit.
−
Take into account that when the
chiller is working, vibrations may be
generated; it is therefore advisable
to install anti-vibration supports
(AVX accessories), fitting them to
the holes in the base according to
the assembly diagram.
−
It is compulsory to provide the
necessary technical spaces, to allow
REGULAR AND EXTRAORDINARY
MAINTENANCE INTERVENTIONS
−
Fasten the unit by checking
carefully that its on the same level;
check that easy access to the
hydraulic and electric part is
allowed.
20.1. MINIMUM TECHNICAL SPACES (mm)
1100
800
800
800
3000
height
WARNING: AL-
WAYS USE ALL
THE PROVIDED
EYEBOLTS
32
INRLPY. 02.10 4086916_01
The unit must be installed by an authorised and qualified technician, in
compliance with the national legislation in force in the country of destination (MD
329/2004).
We shall not be held responsible for any damage whatsoever resulting from the
non-compliance with these instructions.
Before starting any kind of work, it is necessary TO READ CAREFULLY THE
INSTRUCTIONS, AND TO PERFORM THE SAFETY CHECKS TO REDUCE ANY RISK TO A
MINIMUM. All the personnel in charge must know the operations and possible risks
that may arise when all the unit installation operations begin.