11. PRESSURE
DROPS
0,0
50,0
100,0
150,0
200,0
250,0
0
20000
40000
60000
80000
100000
120000
140000
160000
180000
200000
2800
3000
3300
3600
(kPa)
Water flow rate l/h
LOW USEFUL HEAD COLD PREVALENCE (°-L)
11.1. TOTAL PRESSURE DROPS (°-L)
Standard NRL unit (° - L).
The pressure drops include:
−
EVAPORATORS
−
WATER
FILTERS
−
HYDRAULIC
CIRCUITS
Diagrams pressure drops are related to
an average water temperature of 10 °C.
The following table shows the correction
to apply to the pressure drops when the
average water temperature varies
The chiller consists of two hydraulic
circuits per module.
The pressure drops indicated in the
graphics are relative to a single circuit
SINCE THE HYDRAULIC PARALLEL IS IN
CHARGE OF THE CUSTOMER OR THE
PERSON IN CHARGE.
NB:
The water outlet probe (WOP) with its
trap is free, near the electrical box,
remember to insert it in the collector
of the outlet hydraulic parallel, using a
sleeve of ½ inch.
0
50
100
150
200
250
300
350
0
20000
40000
60000
80000
100000
120000
140000 160000
180000
200000
220000
240000
260000
280000
300000
2800
3000
3300
3600
Pressure drops (kPa)
TOTAL COOLING PRESSURE DROP
Water flow rate l/h
21
INRLPY. 02.10 4086916_01