![AERMEC NRL Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/aermec/nrl/nrl_technical-manual-installation-maintenance_2861924013.webp)
5.
STARTING CURRENT REDUCTION IN PRESENCE OF DRE ACCESSORIES
MODEL
SINGLE CIRCUIT
DOUBLE CIRCUIT
THREE-CIRCUIT
FOUR-CIRCUIT
FIVE-CIRCUIT
SIX-CIRCUIT
CURRENT REDUCTION
-30%
-26%
-22%
-20%
-18%
-16%
13
INRLPY. 02.10 4086916_01
6. TECHNICAL
DATA
6.1.
TECHNICAL DATA VERSIONS [°-L]
COOLING
2800
3000
3300
3600
Cooling output
kW
°
676
750
824
898
L
604
672
733
786
Total input power
kW
°
284
322
350
374
L
314
354
384
416
Water flow rate
l/h
°
116270
129000
141730
154460
L
103890
115580
125900
135190
Total pressure drops
kPa
°
73.0
78.6
59.5
58.8
L
59.1
63.8
47.9
45.9
Energy indices
EER
W/W
°
2.38
2.33
2.35
2.40
L
1.92
1.90
1.90
1.89
ESEER
W/W
°
3.76
3.68
3.72
3.79
L
3.65
3.61
3.62
3.59
ELECTRICAL DATA
Fuel feed
A
°
400V - 3 - 50 Hz
L
Input current
A
°
498
572
610
638
L
538
616
656
696
Maximum current
A
°
580
638
716
782
L
Peak current
A
°
789
847
984
1050
L
COMPRESSORS (SCROLL)
Number/Circuit
no./
no.
°
10/4
12/4
12/4
12/4
L
FANS (AXIAL)
Quantity
no.
°
8
8
12
12
L
Air
fl
ow rate
m³/h
°
154000
152000
216600
212400
L
115400
121600
151620
148680
Input power
kW
°
10.0
10.0
15.0
15.0
L
7.5
7.5
11.3
11.3
Input current
A
°
21.6
21.6
32.4
32.4
L
16.2
16.2
24.3
24.3
Useful heads
[1]
Pa
°
45
45
40
40
L
-
-
-
-
FANS (ENLARGED M)
Quantity
no.
°
8
8
12
12
L
Input power
kW
°
13.9
13.9
20.9
20.9
L
-
-
-
-
Input current
A
°
29.6
29.6
44.4
44.4
L
-
-
-
-
Useful heads
[1]
Pa
°
45
45
40
40
L
-
-
-
-
Содержание NRL