16. SAFETY STANDARDS DUE TO GAS R32
To operate on this unit, the personnel must
have a qualification certificate enabling them
to work in contact with flammable gases such
as in this case.
•
All operators working in the cooling
circuit must have obtained the certificate
to be able to work with these gases. This
certificate is issued by the organisation
in authority, and must be recognised
by the company or agency where these
operations are carried out. Otherwise, the
operating technician must be watched
by a third party who possesses this
certification.
•
The unit can be repaired only with the
method suggested by the producer of the
material.
•
The unit must be installed in a space
that respects the minimum allowed
dimensions. Please carefully observe the
following table.
•
Verify that the maintenance area or the
room area meet the requirements on the
label.
•
Verify that the maintenance area is well
ventilated. The ventilation status must be
maintained for the entire duration of the
operation.
Minimum
dimension
of the room
m
2
Quantity of gas filled in "kg"
≤1,2 1,3
1,4
1,5
1,6
1,7
1.8
1.9
2
2,1
2,2
2,3
2,4
2,5
Positioning on the floor
-
14,5 16,8 19,3
22
24,8 27,8
31
34,3 37,8 41,5 45,4 49,4 53,6
Installation in the wall
-
5,2
6,1
7
7,9
8,9
10
11,2 12,4 13,6
15
16,3 17,8 19,3
Installation on the window
-
1,6
1.9
2,1
2,4
2,8
3,1
3.4
3,8
4,2
4,6
5
5,5
6
Installation in the ceiling
-
1,1
1,3
1,4
1,6
1.8
2,1
2,3
2,6
2,8
3,1
3.4
3,7
4