AERMEC FK260 Скачать руководство пользователя страница 14

14

Aermec. 16.01. 5140901_01

9. 

OPERATING TEST

Preparing

 

for the test

• 

Check that the network voltage is correct.

• 

Do not connect the unit to the power supply before installation is 

complete.

• 

Ensure that the connection and supply cables are correctly 

connected to the unit.

• 

Ensure that the gas and liquid pipe valves are open.

• 

 Remove any dust and swarf created during installation.

Running

 

the test

• 

Give voltage to the unit, press the ON/OFF button (by remote 

control) to start the test.

• 

Repeatedly press the MODE button, select COOL, DRY, FAN, etc. and 

check that operation is normal.

• 

Check the operation of the condensate discharge.

Before commissioning the air conditioner, an operating test must be performed. Proceed as follows:

10.  ROUTINE CHECKS FOLLOWING INSTALLATION

ITEMS

 

TO CHECK

POSSIBLE

 

ANOMALY

SITUATION

Is the unit firmly fixed?

The unit could fall, vibrate or generate noise.

Has a check for refrigerant leaks been 

performed?

Poor performance.

Is the thermal insulation sufficient?

It could cause condensate and dripping water.

Does the unit correctly drain the condensate 

water?

It could cause condensate and dripping water.

Does the power supply voltage correspond to 

the one indicated on the label?

Electrical operating fault or damage to 

components which could be blown.

Have the cables and pipes been connected 

correctly and safely?

Electrical operating fault or damage to 

components which could be blown.

Has the unit been safely grounded via an earth 

connection?

Risk of electrocution. Damage to components.

Have the guidelines the manual regarding 

electric cable type and section been followed?

Failure to do so could cause electrical 

operating faults or damage to components 

which could be blown.

Are the air inlet and outlet on the indoor unit 

free of obstacles?

Poor performance.

Have the pipe length and refrigerant charge 

been recorded?

Poor performance. Impossible to check the 

amount of refrigerant added.

Содержание FK260

Страница 1: ...EN USE AND INSTALLATION MANUAL Aermec 16 01 5140901_01 FK260 FK360 Energy efficiency A 5140901_01...

Страница 2: ...NS FOR INSTALLATION OF THE UNIT 10 7 2 POSITIONING 10 7 3 MINIMUM TECHNICAL CLEARANCES 11 7 4 CONDENSATE DRAINAGE 11 7 5 ELECTRICAL WARNINGS 12 7 6 UNIT DIMENSIONS 12 8 WIRING DIAGRAMS 13 9 OPERATING...

Страница 3: ...laws All specifications are subject to change without prior notice Although every effort has been made to ensure precision Aermec does not assume any responsibility for any errors or omissions Dear c...

Страница 4: ...Y ONLY BE FOLLOWED BY SPECIALISED TECHNICIANS OR QUALIFIED PERSONNEL Make sure that other types of coolant do not contaminate the R32 The gas tank must be kept in a vertical position during filling Ap...

Страница 5: ...s Service these operations must only be carried out by Personnel with the specific technical skills Ensure that the power supply and the installed output are adequately scaled to supply the air condit...

Страница 6: ...cally check that the installation conditions of the unit have not been altered and have the system checked by a qualified engineer Do not remove the protection grilles Do not insert your hands or any...

Страница 7: ...remote control Control panel on the machine Compact unit with reduced dimensions Three possible functions Cooling Dehumidification Ventilation only Class A energy efficiency Contained sound emissions...

Страница 8: ...enser attachment diameter mm 7 7 Fan Type Axial Axial Air flow rate m3 h 800 1200 Sound pressure maximum dB A 56 58 Sound pressure medium dB A 54 56 Sound pressure minimum dB A 52 54 Sound power maxim...

Страница 9: ...9 Aermec 16 01 5140901_01 6 DESCRIPTION OF COMPONENTS Inner side Air filter Outer side...

Страница 10: ...the air delivery and intake sockets in the internal part so that air can circulate freely Ensure the installation complies with the minimum technical clearances specified in the installation diagram...

Страница 11: ...re starting up the unit Slide the frame of the unit from the base Install the drainage tub on the corner and fix it with two screws as shown in the figure Connect the drainage pipe NOT provided to the...

Страница 12: ...Ensure that the earthing cable is connected to the building s earthing connection system Ensure that a differential switch suitable for leaks to the ground is installed Do not connect the earth cable...

Страница 13: ...tilator PE W V U N AC L AP1 BN M BU YEGN BU YE RD Kompressor CN1 W V U YEGN 2 XT 1 berstrom ausl ser RD RD WARNUNG 15K 50K 20K CN3 RT1 RT2 RT3 WH BK Temp F hler Lufteintritt Temp F hler Register Temp...

Страница 14: ...e or generate noise Has a check for refrigerant leaks been performed Poor performance Is the thermal insulation sufficient It could cause condensate and dripping water Does the unit correctly drain th...

Страница 15: ...hese steps the filter is still dirty fill a tub with lukewarm water and some non aggressive cleanser and soak it for a few minutes Next dry it with a cloth 5 Otherwise have a specialised technician cl...

Страница 16: ...to select the fan speed 5 SWING button Press this button to select the fan mode from left to right 6 TIMER button Timer function for setting the time the unit is switched on or off Temp function to se...

Страница 17: ...d FAN Ventilation only mode the unit operates in ventilation mode In this case press the FAN button repeatedly to adjust the ventilation speed 3 button Function 1 Pressing or once will increase or red...

Страница 18: ...GRAMMED START UP FUNCTION When the unit is turned off pressed the Timer button to set the programmed start up function The T ON and H icons on the display will start to blink In 5 seconds press the bu...

Страница 19: ...careful not to invert the polarity Close the battery cover NOTE When batteries are replaced use new batteries of the recommended type Remove the batteries if the remote control is not used for extende...

Страница 20: ...room temperature We recommend that you do not keep the air jets direct instead set the unit to Swing mode Make sure the doors and windows are closed well Avoid opening the doors and windows of the roo...

Страница 21: ...ssor protection from overloading Contact specialised personnel or the Aermec Assistance Service L9 Power supply protection Contact specialised personnel or the Aermec Assistance Service H5 Module temp...

Страница 22: ...suggested by the producer of the material The unit must be installed in a space that respects the minimum allowed dimensions Please carefully observe the following table Verify that the maintenance ar...

Страница 23: ......

Страница 24: ...le droit de modifier tous moments les donn es consid r es n cessaires l amelioration du produit Technical data shown in this booklet are not binding Aermec S p A shall have the right to introduce at a...

Отзывы: