• Fan coil preparation:
- Remove the fan coil casing (where present).
ATTENTION: some versions require an
electric connection with a microswitch and/
or the ambient temperature probe located
on the casing. In this case, be careful not to
cut any electrical wires or disconnect the
microswitch connectors, the probe must be
removed carefully from the casing.
- If the installation requires hydraulic connec
-
tions on the right, rotate the coil and move
the electric connections to the left side.
Attention: double-circuit coils are not revers
-
ible, specify the position of the connections
when placing the order.
- Attach the accessories to the fan coil. Refer
to the compatibility table and to the docu
-
mentation of each individual component.
ATTENTION: some accessories cannot be
fitted at the same time on the same unit
(Example 1) or must be combined with other
accessories (Example 2).
Example 1: The VCF valve and the BC4 tray
cannot be installed simultaneously on the
same fan coil.
Example 2: In the event the 3-way VCF valve
is installed, the SW water probe must be
replaced with the SW3 accessory, whose bulb
will be placed on the flow pipe upstream of
the valve.
22.
PREPARATION FOR INSTALLATION
AMP
AMP20
• Fan coil installation:
- The frames of the fan coils are provided
with holes for fixing to the wall.
- To facilitate installation operation, in par
-
ticular for ceiling mounting, support accesso
-
ries AMP and AMP20 are available (refer to
accessories features and their compatibility
with other accessories).
- Fissare il ventilconvettore mediante tasselli
ad espansione.
Expansion bolts must
be chosen based on the weight they have to
withstand and on the wall features.
• Selection of the installation place
- The wall or the ceiling must withstand the weight
of the unit.
- Define the access points of hydraulic connec
-
tions, electric connections and condensate drain
on the fan coil.
- Fan coil connections can be accessed both from
the rear side and from the bottom for units with
cabinet.
Units without casing can also be accessed from
the side.
- Check the quotas of the connections with the
drawing.
- The cardboard of the package can be used as a
template.
- Define where to fix the expansion bolts.
- Choose the expansion bolts adequate to the type
of wall.
FCX_B
FCX_UA
FCX_62U-102U
FCX_17U-56U
Содержание FCX 102
Страница 2: ......
Страница 72: ...72 FCX B U UA UE IFCXBULJ 1412 6456062_01 ML alette motorizzate PXLM FCX 17 22 32 36 42 50 56 U FCX 24 34 44 54...
Страница 77: ...77 FCX B U UA UE IFCXBULJ 1412 6456062_01 WMT10 VCF WMT10 VF VC WMT10 VF RX...
Страница 78: ...78 FCX B U UA UE IFCXBULJ 1412 6456062_01 FM10 VCF FMT10 VF VC FMT10 VF RX...
Страница 79: ...79 FCX B U UA UE IFCXBULJ 1412 6456062_01 FMT21 VCF FMT21 VF VC FMT21 VF RX FMT21 FMT21 FMT21...
Страница 80: ...80 FCX B U UA UE IFCXBULJ 1412 6456062_01 PXAE SIT3 SIT5...
Страница 89: ......
Страница 90: ......