TRANSPORT AND INSTALLATION
Page 17 of 32
Connect condensate drain hose
CAUTION
Material damage / insufficient performance due to improper
connection of condensate drain hose
Handle water collecting tank and condensate drain pipe
with care.
In case of use without water collecting tank:
The rear hose end must be in a lower position than the
front hose end (drain pipe): minimum slope 5%, i. e.
5 cm / metre.
Do not immerse the hose end in water (water back-up
may occur).
Never bend the hose.
Do not place any objects on the hose.
Check regularly whether condensate is properly
discharged.
1. Remove the water collecting tank from the rocker.
2. Attach the condensate drain hose to the condensate drain pipe (Fig. 2, item 3)
and fix it with a hose clamp.
3. Lay the hose with a slope (min. 5%, i.e. 5 cm / per metre) from the air
dehumidifier to an outlet.
If the air dehumidifier is installed on a wall bracket or in any other
elevated position, the hose can also be directed down through the
hole in the rocker.