10 / 36
TF6089_B
Aereco S.A.
3.2.4. DUCT CONNECTIONS TO THE DXR UNIT
AND TO THE DX HUB
The connections to the DXR Unit are all in Ø160 mm. Labels on the unit identify the 4 ducts to be
connected (fresh air, used air, supply air, exhaust air).
Outdoor fresh air and used air ducts must
be insulated.
Be careful to respect top and bottom of the installation.
Fresh air
(outdoor)
Used air
(outdoor)
Fresh air supply
(indoor)
Exhaust air
(indoor)
Labels on the unit identify the 4 ducts to be connected (fresh air, used air, supply air, exhaust air).
Either on the DX Hub 5 or on the DX Hub 6, it is possible to choose one inlet among a
choice of 2 (DX Hub 5) or 3 (DX Hub 6).
Firstly the foam has to be cuttered then the metal part can be swinged in order to remove
it. Then as the assembling part of the DXR's spigot, the inlet spigot has to be screwed
and sealed to the DX Hub.
The seal can be made thanks to silicone seal.
1
1
1
1
2
2
2
3
1 or 3
4
5
1
Ø100 mm or Ø75 mm
2
Ø100 mm or Ø125 mm
3
Ø125 mm
4
Ø160 mm
5
Ø160 + 50 mm insulation
SDC100
SDC
125
SDC100
SDC100
SDC100
BXC
BXC
BXC
compensation
to exhaust air outlet
to fresh air inlet
Supply:
rigid or semi-rigid duct
+ flexible connection to the unit (1 m max)
(avoid noise in the room)
Exhaust air:
rigid (avoid pressure drop)
or semi-rigid duct
Air intake and air outlet:
insulated rigid
duct (avoid pressure drop and condensation)
Duct diameters and recommendation concerning the type of ducts