Innovation Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 6 – MAINTENANCE
OMM-0078_0M
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
87
of
216
GF-128
Phone: 800-526-0288
09/11/2015
Figure 6-8. Anode Assembly and Combustion Chamber Head
6.8 HEAT EXCHANGER CLEANING
For hard water installations, AERCO high recommends use of its Scale Reducer system. The
Scale Reducer, model SR300, is strongly recommended for installations in areas with hard water
(>3.5 grains/gal, >59.9 mg/L). It provides an economical, maintenance free treatment of hard
water without the use of salt or any chemicals. The SR300 prevents new scale build-up and
eliminates existing build-up in water heaters, boilers and storage tanks, hot water piping, valves,
recirculation lines and pumps, mixing valves, showerheads and other plumbing fixtures. This
eliminates the associated heat exchanger overheating and lets the water heater continue to
perform at its peak efficiency (low-water heating cost). In addition to reduced inspection
frequency, the periodic maintenance to remove and flush the water heater for scale deposits is no
longer necessary.
Alternatively, AERCO recommends
that the heat exchanger of the unit be cleaned annually to
maintain maximum heat transfer efficiencies using a solution of HydroSkrub and water.
HydroSkrub is distributed by AERCO International, Inc. and is designed to dissolve the toughest
water scale, lime, mud and rust deposits from virtually any type of water-based equipment.
CAUTION
Please review MSDS, specifications, and our website (
www.aerco.com)
for
additional information, or call technical service at (800) 526-0288.
CAUTION
Do not drain the unit without venting the shell! A vacuum in the unit may displace
the head liner causing serious damage not covered by warranty.
3/8-16 HEX
BOLTS
(2 Each)
5/16-24 POSITIONING BOLT
(1 Each)
1/4-20 HEX BOLT
(4 Each)
COMBUSTION
CHAMBER
HEAD
COMBUSTION
CHAMBER
HEAD
LIFTING HOOK
SUPPORT
BRACKET