APPENDIX A – INNOVATION MENU ITEM DESCRIPTIONS
Table A-1: Operating Menu Item Descriptions
Table A-1:
OPERATING MENU ITEM DESCRIPTIONS
See section 3-4 for a range of choices and the default values.
MENU LEVEL & OPTION
DESCRIPTION
1 Active Setpoint
This is the setpoint temperature to which the control is set
when operating in the Constant Setpoint or Remote Setpoint
mode. When in the Constant Setpoint mode, this value is
equal to the Internal Setpoint setting in the Configuration Menu.
When in the Remote Setpoint mode, this value is the setpoint
equivalent to the remote analog signal supplied to the unit
2 Inlet Temp
Displays Inlet Water Temperature
3 Air Temp
For monitoring purposes only
4 Outdoor Temp
Displayed only if outdoor sensor is installed and enabled.
5 Valve Position In
Desired input valve position. This is normally the same as the
valve position shown on the bargraph when the heater is
operating.
6 Exhaust Temp
Displays Exhaust Gas Temperature
7 Valve Position Out
Displays actual real time Valve Position
8 FFWD Temp
Displays Feed Forward Water Temperature
9 Flame Strength
Displays flame strength from 0% to 100%.
10 Oxygen Level
Displays the Oxygen Level of combustion exhaust gasses
11 Ignition Time
Displays the elapsed time between confirmation of gas valve
opening (POC) until a stable flame is detected
12 SSOV Time to OPN
Displays the elapsed time between 120VAC being applied to
the Gas Valve and confirmation of gas valve opening (POC)
13 Run Cycles
Displays the total number of run cycles from 0 to 999,999.
14 Run Hours
Displays total run time of unit in hours from 0 to 9,999,999.
15 Fault Log
Displays information on the last 20 faults (0 – 19).