Innovation Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 7 – TROUBLESHOOTING GUIDE
Page
106
of
216
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0078_0M
09/11/2015
Phone: 800-526-0288
GF-128
TABLE 7-1. WATER HEATER TROUBLESHOOTING – Continued
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
(continued)
3.
Switch wired incorrectly.
4.
Defective Power Supply Board or
fuse
5.
Defective IGST Board
3.
If the switch is wired correctly, replace the switch.
4.
Check DS1 & DS2 LEDs on Power Supply Board. If they are not
steady ON, replace Power Supply Board.
5.
Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF
every second. If not, replace IGST Board.
PRG SWTCH OPEN
DURING PURGE
1.
Defective purge switch.
2.
No voltage present at switch.
3.
Switch wired incorrectly.
4.
Defective Power Supply Board or
fuse
5.
Defective IGST Board
1.
If the air-fuel valve does rotate, check purge switch for continuity
when closing. Replace switch if continuity does not exist.
2.
Measure for 24 VAC from each side of the switch to ground. If
24VAC is not present, refer fault to qualified service personnel.
3.
Check to ensure that the switch is wired correctly (correct wire
numbers on the normally open terminals).
4.
Check DS1 & DS2 LEDs on Power Supply Board. If they are not
steady ON, replace Power Supply Board.
5.
Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF
every second. If not, replace IGST Board.
OUTDOOR TEMP
SENSOR FAULT
1.
Loose or broken wiring.
2.
Defective Sensor.
3.
Incorrect Sensor.
1.
Inspect Outdoor Temperature sensor for loose or broken wiring.
2.
Check resistance of sensor to ensure it is within specification.
3.
Ensure that the correct sensor is installed.
RECIRC PUMP FAILURE
1.
Internal recirculation pump failed.
7. Replace recirculation pump.
REMOTE SETPT
SIGNAL FAULT
1.
Remote setpoint signal not present:
Not yet installed.
Wrong polarity.
Signal defective at source.
Broken or loose wiring.
2.
Signal is not isolated (floating) if 4 to
20 mA.
3.
Control Box signal type selection
switches not set for correct signal
type (voltage or current).
1.
Check I/O Box to ensure signal is hooked up.
Hook up if not installed.
If installed, check polarity.
Measure signal level.
Check continuity of wiring between source and unit.
2.
Check signal at source to ensure it is isolated.
3.
Check
DIP
switch on PMC board to ensure it is set correctly for
the type of signal being sent. Check control signal type set in
Configuration Menu.