GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
NOTE
Whenever “
CODE NO.
” is displayed, it indicates that the valid
password must be entered. This is accomplished by entering code
0000
(four zeros) by pressing the Program Key four (4) times.
Table 4-3: EXPERT Menu Listing
FUNCTION
DESCRIPTION
ENTRY RANGE
DEFAULT
INSTALLATION Sub-Menu
CODE-NO
Permits entry of valid Code No.(0000)
0000 - 9999
0000
BUS ID HS
BUS ID HS
MUST
be set to - - - - to operate
the boiler
01 - 08
DO NOT
CHANGE
BUS ID 1
The heating circuits are sequentially
numbered starting with “01“, heating circuit
numbers must not be assigned twice.
(00), 01 – 15
01
BUS ID 2
Heating circuits are sequentially numbered
starting with “01“, heating circuit numbers
must not be assigned twice.
(00), 01 – 15
- - - -
AF SUPPLY
Outdoor sensor power supply
00, 01 (OFF/ON)
01 (ON)
BUS TERM
Bus terminating resistor
(Must be set to 01)
00, 01 (OFF/ON)
01 (ON)
EBUS
SUPPLY
Switches the Ebus supply ON/OFF
00, 01 (OFF/ON)
01 (ON)
TIME
MASTER
Not Applicable
MAX T-COLL
Sets the maximum allowable header set
point temperature.
86.0°F – 230.0°F
185.0°F
MIN T-COLL
Sets the minimum allowable header set point
temperature.
50.0°F – 176.0°F
50.0°F
MAX T-HS2
Not Applicable
MIN T-HS2
Not Applicable
V-CURVE
0 to 10 Volt input Voltage curves. Choose
from preset curves (see Section 4.4.1) or
customize a curve.
00 – 11
11
CURVE 11-U1
Low voltage setting
0.00V – 10.00V
0.000
CURVE 11-U2
High voltage setting
0.00V – 10.00V
10.00
CURVE 11-T1
Minimum set point temperature
32.0°F – 248.0°F
59.0°F
CURVE 11-T2
Maximum set point temperature
32.0°F – 248.0°F
185.0°F
CURVE 11-UO
Stop/Start voltage level. Going below/above
this setting will stop/start the Boiler.
0.00V – 10.00V
1.00