06/05/13
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
•
Ph: 800-526- 0288
Page
49
of
112
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
5.3.2 Configuring Remote Signal Source
Configure the Remote Signal Source as shown in the instructions below.
Configuring Remote Signal Source
1. Ensure ON/OFF switch on front of Modulex boiler is in the ON position.
2. Open Controller front panel.
3. Turn Rotary Knob clockwise to
EXPERT
menu. The first sub-menu displayed will be
INSTALLATION
(sub-menu items scroll in this sequence:
INSTALLATION
,
HOT
WATER
,
HEAT CIRCUIT 1
,
HEAT CIRCUIT 2
,
SOLAR / MF
). Continue scrolling
(clockwise) through the
EXPERT
menu until
SOLAR / MF
is displayed.
4. With
SOLAR / MF
displayed, press the Program Key to enter the
SOLAR / MF
sub-menu.
5. Scroll through the
SOLAR / MF
sub-menu by turning Rotary Knob clockwise until the
F-15
FUNCTION
is displayed along with it’s presently stored value (default is 00).
6. Press Program Key to change the F-15
FUNCTION
. Display will show
CODE NO.
,
requesting valid code to be entered.
7. Enter code
0000
(four zeros) by pressing the Program Key four times. The red LED will
remain lit while the four code digits are entered.
8. With
F-15 FUNCTION
displayed again and red LED lit, turn Rotary Knob to change the
F-
15 FUNCTION
to 01.
9. Press the Program Key to store the 01 setting for the
F-15 FUNCTION
. The red LED will
go off.
10. Continue scrolling through the sub-menu until
RETURN
is displayed.
11. Press the Program Key to exit the
SOLAR / MF
sub-menu.
12. With SOLAR / MF displayed, turn Rotary Knob counter-clockwise until the
INSTALLATION
sub-menu is displayed in the LCD.
13. With
INSTALLATION
displayed in the LCD, proceed directly to
paragraph 5.3.3
.
NOTE
When navigating the menus during configuration and you scroll
past the SOLAR / MF item, the EXPERT HS menu will be
displayed. If this occurs, slowly turn the Rotary Knob
counterclockwise until SOLAR / MF is again displayed.