Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
Table 4-2: USER Menu Listing
FUNCTION
DESCRIPTION
ENTRY RANGE
DEFAULT
INSTALLATION Sub-Menu
LANGUAGE
Selects display language.
12 languages are
available.
ENGLISH
CONTRAST
Adjusts display contrast
-20 to 20
00
DISPLAY
SEL
Sets the day of the week or the sensor
temperature (°F) to appear in the display when
the swing-down panel is closed.
Day:
SUN – SAT
T-OUTSIDE:
Outside Temperature
FLOW TEMP (1/2):
Flow Temp. For Heating
Circuit 1 or 2 supply
water temperature. (Only
if sensor is installed)
T-DHW:
Domestic Hot Water
Temperature.
T-BOILER;
Boiler Outlet Temperature.
T-ROOM (1 / 2):
Room Temp, Heating
Circuit 1 or 2 (ONLY if
Remote Control is
connected).
See
DESCRIPTION
Column
- - - -
RETURN
Press Program Key to exit INSTALLATION Sub-
Menu.
HOT WATER Sub-Menu
1X DHW
Not Applicable
T-DHW 1
Hot Water set point
50°F - 158°F
140°F
T-DHW 2
Not Applicable
T-DHW 3
Not Applicable
BOB-VALUE
Not Applicable
CIRCL-P-
DHW
Not Applicable
RETURN
Press Program Key exit HOT WATER Sub-
Menu.