GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
MONTH
Set current month
00-12
DAY
Set current day of month
00-31
CONF DEVICE
Confirm Device
- - - -, 01 – 06
- - - -
HEATSOURCE 1
Heat Source 1
00 – 06
06
HS1 BUS
Heat Source 1 Bus
00 – 04
02
HEATSOURCE 2
Heat Source 2
00 – 05
00
STORAGE HS2
Storage Heat Source 2
00 – 03
00
BUFFER
Buffer
00, 01, 02
00
HC FUNCTION 1
Heating Circuit Function 1
00, 01, 03
00
HC FUNCTION 2
Heating Circuit Function 2
00 – 04
00
CAP/MODULE
See
Paragraph 4.8.1
for instructions.
00 – 1000 Kw
40 Kw
RELAY FUNC 1
Relay Function 1 (See
Paragraph
4.8.2
)
00 – 26
00
T-MF1 SETP
Temperature – Multifunction Relay 1
Setpoint
86°F – 194°F
86°F
MF1 HYST
Multifunction Relay 1 Hysteresis
4°F – 18°F
9°F
RELAY FUNC 2
Relay Function 2 (See
Paragraph
4.8.2
)
00 – 26
00
T-MF2 SETP
Temperature – Multifunction Relay 2
Setpoint
86°F – 194°F
86°F
MF2 HYST
Multifunction Relay 2 Hysteresis
4°Ra – 18°Ra
9°F
RELAY FUNC 3
Relay Function 3
00 – 26
01
T-MF3 SETP
Temperature – Multifunction Relay 3
Setpoint
86°F – 194°F
86°F
MF3 HYST
Multifunction Relay 3 Hysteresis
4°F – 18°F
9°F
RELAY FUNC 4
Relay Function 4
00 – 26
02
T-MF4 SETP
Temperature – Multifunction Relay 4
Setpoint
86°F – 194°F
86°F
MF4 HYST
Multifunction Relay 4 Hysteresis
4°F – 18°F
9°F
BUS ID 1
Bus Identification No. 1
00 – 15
01
BUS ID 2
Bus Identification 2
00 – 15
02
5K SENSOR
5,000 Ohm Sensor
00=5K, 01=1K
00 = 5 K
4.7.1 CAP/MODULE Function (Maximum Kilowatts per Burner)
When the Program Key is pressed with CAP/MODULE displayed, the display may show
“SCAN”, indicating that the Controller is searching for related MODULE (BOILER) functions.
Once the scan is complete, follow instructions below.
CAP/MODULE Function (Setting Max. Kw per Burner)
1. Press the Program Key. The display will show CODE NO., requesting the valid code to be