Benchmark 6000 Boiler Installation, Operation & Maintenance Manual
CHAPTER 3 – OPERATION
Page
48
of
210
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0086_0D
03/20/14
Ph.: 800-526-0288
GF-133
The Items contained in group 1 (BST Monitor Items) are ALWAYS displayed within the menu, as
these items are critical for proper system operation. Therefore, the BST Monitor Items Header
itself is NOT displayed.
The Items contained in groups 2-5 are NOT DISPLAYED unless that particular item group has
been enabled from the C-More keypad.
Table 3-7: BST Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
BST Mode
Off
BST Slave
BST Master
Off
BST Setpoint
BST Setpt Lo Limit
BST Setpt Hi Limit
130°F
Header Temp
NA
Header Temp
(°F)
BST Fire Rate
0
100%
Fire rate %
BST Ave Fire Rate
0
100%
Avg Fire Rate %
BST Outdoor Temp
NA
Outdoor Temp
(°F)
Units Available
0
8
Units Present
Units Ignited
0
8
Units firing
BST Valve State
0 (CLOSED)
1 (OPEN)
0
1 Comm Errors 8
0
9
0
1 BST Units 8
0 (see table)
0 (see table)
0
*BST SETUP MENU*
Disabled
Enabled
Disabled
BST Setpoint Mode
Constant Setpoint
Remote Setpoint
Outdoor Reset
Constant Setpt
Head Temp Source
Network
FFWD Temp
FFWD Temp
Header Temp Addr
0
255
240
Header Temp Point
0
255
14
BST Outdoor Sens
Disabled
Enabled
Disabled
Outdr Tmp Source
Outdoor Temp
Network
Outdoor Temp
Outdoor Tmp Addr
0
255
240
Outdoor Tmp Pnt
0
255
215
BST Remote Signal
4-20 mA/1-5 Vdc;
0-20 mA/0-5
Vdc;
Network
Network
BST Auto Mstr
No
Yes
NOTE! A Modbus temperature
transmitter must be installed in
conjunction with this feature.
No
BST Auto Timer
10 sec
120 sec
30 sec
Remote Intlk Use
Boiler Shutdown
System Shutdown
System
Shutdown
One Boiler Mode
Off
On-Outlet
Temp
On-Avg Temp
Off
1 Blr Threshold
10
35
25
Setpoint Setback
Disable
Enable
Disable