Benchmark 6000 Boiler Installation, Operation & Maintenance Manual
CHAPTER 9 – RS-232 COMMUNICATION
Page
132
of
210
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0086_0D
03/20/14
Ph.: 800-526-0288
GF-133
MENU PROCESSING UTILIZING RS-232 COMMUNICATION – Continued
NOTE
The Level 1 password (
159
) must be entered to change options in
the Setup, Configuration and Tuning Menus. The Level 2
password (
6817
) must be entered to view or change options in the
Calibration and Diagnostics Menus.
With the exception of the password entry, all other keyboard
entries can be made using either upper or lower case.
11.
To view the available menus in the top-down sequence shown in Figure 3-2, enter
M
<Rtn>
. The Menu title and first 10 options will be displayed.
12.
When viewing menus containing more than 10 options, enter
N <Rtn>
to display the
remaining options.
13.
Shortcut keys are also available to go directly to a specific menu. These shortcut keys
are:
m0
= Default (Operating) Menu
m1
= Setup Menu
m2
= Configuration Menu
m3
= Tuning Menu
m4
= Calibration Menu
m5
= Diagnostic Menu
14.
To change a value or setting for a displayed menu option, proceed as follows:
(a) Enter
C
, followed by the number to the right of the displayed option to
be changed, and then press
<Rtn>
.
(b) Enter the desired value or setting for the option and press
<Rtn>
. Refer
to Chapter 3, Tables 3-2 through 3-5 for allowable entry ranges and
settings for the Operating, Setup, Configuration and Tuning Menus.
(The Calibration and Diagnostic Menus should only be used by Factory-
Trained service personnel).
(c) Menu changes will be stored in non-volatile memory.
15.
To redisplay the menu and view the option which was just changed in step 5, enter
D
and press
<Rtn>.
16.
To display the Fault (F) Log, Sensor (S) Log or Time (T) Line Log, press
F
,
S
or
T
followed by
<Rtn>.
Refer to paragraph 9.4 for descriptions and samples of these data
logs.
17.
To log off and terminate the RS-232 communication link, press
L
followed by
<Rtn>.
9.4 DATA LOGGING
During operation, the C-More Control Panel continuously monitors and logs data associated
with operational events, faults and sensor readings associated with the boiler system.
Descriptions of these data logs are provided in the following sections. The basic procedure for
accessing each data log is described in section 9.3 step 10.