SECTION 2: OPERATION
Page
18
of
144
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0128_0B
07/17/2017
Ph.: 800-526-0288
2.5 SETUP Menu
The
Setup
menu permits the operator to enter the unit password (159) which is required to
change the menu options. To prevent unauthorized use, the password will time-out after 1 hour.
Therefore, the correct password must be reentered when required. In addition to permitting
password entries, the
Setup
menu is also used to enter date and time, and units of temperature
measurements. A view-only software version display is also provided to indicate the current C-
More Controller software version.
A full description of each item appears in Appendix A-2.
TABLE 2-3: SETUP Menu
MENU ITEM DISPLAY
AVAILABLE CHOICES OR LIMITS
DEFAULT
Minimum
Maximum
1
Password
0
9999
0
2
Language
English
English
3
Time
12:00 am
11:59 pm
12:00
4
Date
01/01/00
12/31/99
01/01/00
5
Unit of Temp
Fahrenheit or Celsius
Fahrenheit
6
Comm Address
0
127
0
7
Baud Rate
2400, 4800, 9600, 19.2K
9600
8
onAER Mode
Ethernet or SD Card
Ethernet
9
Min Upload Timer
0
9,999 Sec
0
10
Unit Alpha
E, G, H, R, N or A
A
11
Unit Year
0
99
0
12
Unit Serial #
0
9999
0
13
Software
Ver 0.00
Ver 9.99
Current software
version