TABLE 2-10: Calibration Menu
MENU ITEM DISPLAY
AVAILABLE CHOICES OR LIMITS
DEFAULT
Minimum
Maximum
32
Gas Press Reset
Automatic or Manual
Manual
33
Min Off Time
0 Min
15 Min
1 Min
34
Heatr Tuning Dsp
Enabled or Disabled
Disabled
35
Heatr Bkpt Dsp
Enabled or Disabled
Disabled
36
Stop Level
0%
Start Level
16
37
Start Level
Stop Level
40%
22
38
Skip Range Cntr
10
95
40
39
Skip Range Span
0
3
0%
40
Skip Speed
0.5
2.0
0.5%
41
O2 Gain
0.500
1.500
1.000
42
O2 Offset
-24.0
+2.0
1.0
43
O2 Sensor
Enabled or Disabled
Depends on unit type/size
44
Cal Temp Sensors
Off or Start
Off
45
FFWD Temp Offset
-20
+20
0
46
Exhst Tmp Offset
-20
+20
0
47
Outdr Air Offset
-20
+20
0
48
Inlet Air Offset
-20
+20
0
49
Inlet Wtr Offset
-20
+20
0
50
Outlet Wtr Offset
-20
+20
0
51
24 hr Max Cycles
0
9999
0
52
24 hr Max Ovrtemp
0
9999
0
53
0-10v Out Test
0.0
10.0
0.00
54
Spark Monitor
Enabled or Disabled
Depends on unit type/size
55
Min Spark Amps
0.0 Amps
2.5 Amps
0.10 Amps
56
Max Spark Amps
0.0 Amps
2.5 Amps
0.40 Amps