Benchmark 750-3000 Boiler Operation, Service, Maintenance Guide - KOREA
APPENDIX A: BOILER MENU DESCRIPTION
OMM-0128_0A
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
81
of
144
GF-206-K
Ph.: 800-526-0288
07/17/2017
TABLE A-6: CALIBRATION Menu Item Descriptions
MENU OPTION
DESCRIPTION
46
– Exhst Tmp Ofset
Range: -20 to + 20 (either ºF or °C)
47
– Outdr Air Offset
Range: -20 to + 20 (either ºF or °C)
48
– Inlet Air Offset
Range: -20 to + 20 (either ºF or °C)
49
– Inlet Wtr Offset
Range: -20 to + 20 (either ºF or °C)
50
– Outlet Wtr Offset
Range: -20 to + 20 (either ºF or °C)
51
24 hr Max Cycles
Maximum cycles in 24 hour period.
52
24 hr Max Ovrtemp
Maximum over-temp in 24 hour period.
53
0-10v Out Test
Set the blower voltage at 0-10v for testing.
54
Spark Monitor
Enables or disables the Spark Monitor function, which displays
the AC current on the input of the Ignition Transformer.
56
Min Spark Amps
Allows the adjustment of the minimum spark current required at
the spark transformer input.
56
Max Spark Amps
Allows the adjustment of the maximum spark current required at
the spark transformer input.