Power Quality Analyzer Model 3945
27
4.1.5 Electrical
Hookup
(electrical
network)
• Highlight ELECTRICAL HOOKUP with the
buttons, then press the
button. The following screen will appear:
N
L1
Single-phase
N
L1
L2
Two-phase
N
L1
L2
L3
3 phase-3 wire
(DELTA)
N
L1
L2
L3
3 phase-4 wire
(WYE)
07/25/02 10:26
100%
Figure 4-3
• Choose the hookup type with the
and
buttons.
• Press
the button to apply the new hookup selection. The Confi guration menu
will once again be displayed on the screen.
Hookup Types:
Single or two-phase:
The neutral current is not measured or calculated.
3 phase - 3 wire:
- DELTA network: Only power totals are representative of the actual situation.
- WYE network: The neutral current is not calculated. It is necessary to
connect neutral to obtain representative power levels per phase.
3 phase - 4 wire:
The neutral current is available and its value and wave-
form are displayed.
V1 must be connected in all hookups, since the display is synchro-
nized from V1 and the network frequency measured by V1.
Synchronization of the Display in “Waveform” mode:
Display selection
(vertical right menu)
Reference channel
for synchronization
3U
3V
4A / 3A
L1
L2
L3
U1
V1
A1
V1
V2
V3