Clamp-on Ground Resistance Tester Model 6416
33
6.1.3
General Information
This information is displayed in both Standard and Advanced modes.
PRODUCT ZxI GREATER THAN 50 V
■
The blinking NOISE symbol is
displayed.
■
The impedance blinks.
■
The hazardous voltage symbol blinks.
Figure 6-5
IMPEDANCE GREATER THAN 1500 Ω
In this case:
■
The impedance display indicates O.R
(Over Range).
Figure 6-6
LEAKAGE CURRENT DISTURBANCE
I
f the current is greater than 5 A, or if it is
significantly disturbed:
■
The blinking NOISE symbol is
displayed.
■
The impedance blinks.
Figure 6-7
CURRENT GREATER THAN 10 A
If the current is greater than 10 A:
■
The blinking NOISE symbol is
displayed.
■
The impedance is replaced by
- - - -
Figure 6-8