Table 13: Output Possibilities at the Analog Output
Terminals
The T0 time (in PC mode) can be set easily and precisely via the help of the PC program or
via the bus system.
8.5 Potentiometer R310
If the Thyro Power Manager is configured without a PC program and bus system (S1.8 OFF),
the limiting value for network load optimization and for the three converter inputs can thus be
set via Poti R310. The standard default setting is 200% and the Poti is turned to its right-
hand blocked position. The same limiting value is used for all three inputs per Poti. A unique
limiting value can be determined for each one of the 3 converters via a PC program or via the
bus system (in PC mode).
As the potentiometer does not possess a scale, one can deploy analog output 6 (X8.1 / X8.2)
as help for the setting (connect the voltmeter, range 0 – 10V). If the potentiometer is
changed, (no PC mode) the analog output is automatically switched over to the output of the
potentiometer value. In the course, meaning here 5V = 100% (type value of converter), the
adjustment interval ranges between 0 – 200% (0 – 10V).
In PC mode (S1.8 = closed), the switches and potentiometer settings are
mostly ignored and only those values are used, which are stored and set via
a PC program. In this case, a potentiometer change e.g. does not incur a
change of values and the setting help is not activated!
T
0
[s] (50Hz): T
0
[periods]:
Analog[V]:
0.2
10
0.5
0.4
20
1
0.6
30
1.5
0.8
40
2
1
50
2.5
1.2
60
3
1.4
70
3.5
1.6
80
4
1.8
90
4.5
2
100
5
4
200
5.36
6
300
5.71
8
400
6.07
10
500
6.43
15
750
7.32
20
1000
8.21
25
1250
9.11
30
1500
10