45
Relay Alarms/Status
Status
M1
LED
Pins Status Name Status
RL1
Alarm =
A30 COMMON ALARM
Not energized
if alarm is
present
2 – 3 Closed
DL1
On
1 – 2 Open
RL2
Alarm =
A1 MAINS FAULT
Not energized
if alarm is
present
5 – 6 Closed
DL2
On
4 – 5 Open
RL3
Alarm =
A9 BATTERY AUT END
Not energized
if alarm is
present
8 – 9 Closed
DL3
On
7 – 8 Open
RL4
Alarm =
A13 INV OUT OF TOL
Not energized
if alarm is
present
11 – 12 Closed
DL4
On
10 – 11 Open
RL5
NORMAL MODE
Alarm =
A16 BYPASS
LOAD
Not energized
if alarm is
present
14 – 15 Closed
DL5
On
ECO MODE
Status =
S7 BYPASS
LOAD
Energized
if status is
present
13 – 14 Open
RL6
BATTERY NOT
DISCHARGING
Not energized
if battery
discharge
17 – 18 Closed
DL6
On
16 – 17 Open
RL7
NORMAL MODE
Status =
S4 INVERTER
LOAD
Energized
if status is
present
20 – 21 Closed
DL7
On
ECO MODE
Alarm =
A38 INV
LOAD
Not energized
if alarm is
present
19 – 20 Open
RL8
Status =
S6 BYPASS OK
Energized
if status is
present
23 – 24 Closed
DL8
On
22 – 23 Open
Relay output characteristics:
120 VAC voltage 1 A current
50 VDC voltage 1 A current resistive load