53
9
START UP
FROM MBCB
CLOSE OCB
Close OCB
The load is fed by the static bypass
switch. Circuit breaker MBCB is still
closed. LED #7 lit green.
10
START UP
FROM MBCB
CLOSE MBCB
Open MBCB
The load is fed by the static bypass switch
and the inverter can be started. LED #8
off.
11
INVERTER
START WAIT
PLEASE
The modulation of the inverter bridge is
started. The AC voltage reaches the
nominal value. The microprocessor
checks the synchronization with the
bypass line.
12
START UP
FROM MBCB
MOVE BYP –
SWITCH
Move the
selector
“NORMAL-
BYPASS” to
NORMAL
The load is transferred to the inverter.
LED #5 lit green.
13
START UP
END WAIT
PLEASE
The microprocessor checks that all the
output parameters (voltage, current,
frequency) are within the tolerance limits
14
UPS MODEL
OUTPUT
VOLTAGE