4-10
4-6-2 Wiring (Single Unit, 80kVA model shown)
Wiring procedure:
1. Remove the terminal cover at the rear side. See Fig. 4-1.
2. You can see the terminal block with marks as below.
Input: L1, L2, L3 and neutral
Bypass: L1, L2, L3 (for Bypass neutral use the Input neutral terminal)
Output: L1, L2, L3 and neutral
External Battery: po), negative(-) and neutral
Grounding
Terminal:
Protection
3. The rated voltage of standard model is 220/380VAC, 230/400VAC or 240/415VAC.
4. The battery rating voltage is ±240VDC.
5. Confirm if the input and bypass input circuit breakers (Q1 and Q2) are cut off (Refer
to Fig.4-2).
Remove
Cover
Main AC Input
Bypass Input
External Battery
Output
Grounding
Terminal
Fig. 4-1 Wiring Terminal