BC-N4 Glycol Chiller
Page: 51
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: [email protected]
G.
EVAPORATOR: The evaporator is a brazed plate heat exchanger where the refrigerant
liquid is allowed to evaporate (boil off) to absorb heat (BTU) from the process fluid. As the
heat is absorbed, the process fluid is chilled.
H.
CAPACITY CONTROL SOLENOID: The chiller is equipped with a capacity control
feature. The capacity control feature matches the chiller capacity to the cooling load
to provide temperature control and to prevent short cycling of the compressor. Units
with digital scroll compressors (M1D) use a solenoid valve to unload the compressor
to a low as about 20% capacity. Units without a digital scroll
compressor use a hot gas bypass solenoid valve to reduce the
chiller capacity to about 50%.
I.
HIGH/LOW PRESSURE SWITCH: The high and low pressure
switches protect the refrigeration system from usage operating
conditions. Units may be equipped with either an adjustable or
non-adjustable ‘fixed’ high and low pressure switches.
The
high pressure switch is factory set and protects the
refrigeration components and personnel from potential
damage and injury from excessive pressure. The high
pressure safety must not be altered in the field for any reason
(see section 8.1 for factory settings.
The
low pressure switch is factory set to open at 32°F and
to close at 36°F - 38°F*. The low pressure switch protects
the chiller from damage caused by low refrigerant pressure
operating below the cooling fluid’s freeze point.
NEVER LOWER THE CUT OUT SETTING WITHOUT ADDING GLYCOL TO THE
CIRCULATING SYSTEM. EVAPORATOR DAMAGE WILL RESULT AND WILL NOT BE
COVERED BY THE WARRANTY.
Adjustable low pressure switch
Adjustable high pressure switch
Typical placement of non-adjustable “fixed” pressure switches.
Non-adjustable “fixed”
low pressure switch
Non-adjustable “fixed”
high pressure switch
* See Temperature-Pressure
chart in Section 8.5 for
refrigerant pressure.
Содержание BC-N4 Series
Страница 2: ......
Страница 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Страница 20: ...Page 20 THIS PAGE INTENTIONALLY BLANK ...
Страница 32: ...Page 32 THIS PAGE INTENTIONALLY BLANK ...
Страница 48: ...Page 48 THIS PAGE INTENTIONALLY BLANK ...
Страница 54: ...Page 54 THIS PAGE INTENTIONALLY BLANK ...
Страница 62: ...Page 62 THIS PAGE INTENTIONALLY BLANK ...
Страница 63: ...END 2016 ADVANTAGE ENGINEERING INC RE 09 27 2016 ...
Страница 64: ......