BC-N4 Glycol Chiller
Page: 23
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: [email protected]
3.
WATER QUALITY CONTROL. Lack of, as well as, improper water treatment can
damage the chilling unit. The services of competent water treatment specialist
should be obtained and their recommendations followed. It is the equipment
owner’s responsibility to prevent damage from foreign material or inadequate
water treatment. See water treatment section in section 1.6 of this manual for
more information.
4.
FOR AUTOMATIC FILL: Available as an option
in non freeze climates. Always install a manual
shut off valve on the make-up water supply
(if equipped on the outside of the unit. When
electrical power is applied to the unit but the On/
Off Selector is in the ‘off’ position open the owner
supplied shut off valve. The level switch will
activate the make-up solenoid, which will open
and the water supply will fill the reservoir tank.
Do not use automatic fill when operating at
temperature below 48°F.
5.
MANUAL FILL: Disconnect and lock out the
electrical power supply and remove all necessary
cover panels to access the reservoir. Add fluid
directly to the reservoir. When the pump is
first started, as process lines are filled and air
is purged, additional fluid may be required to
restore the reservoir to the correct level. Verify
reservoir level via the coolant sight glass .
6.
Do not use deionized water in this unit unless
your unit was specifically designed for use with
deionized water. Consult factory if not certain.
B.
PROPER ROTATION (PHASING) OF SCROLL
COMPRESSORS & PUMPS & FANS
1.
Correct compressor, fan (on air-cooled units) and
pump rotation is critical for unit performance and
to avoid severe damage to the compressor.
2.
All portable chiller compressors and pumps will be set to rotate in the same
direction during the testing process at the factory.
3.
After electrical installation the rotation must be checked by observing the pump
motor shaft on the end of the pump and comparing its rotation to the directional
arrow on the motor. If the rotation needs to be changed it should be done at the
main power entry by switching any two power conductors at the terminal block or
customer supplied main power disconnect. Recheck rotation before operating the
units.
4.
Caution must be taken when checking rotation to avoid electrical shock.
5.
A scroll compressor may make a loud rattling noise when rotating in the wrong
direction.
Typical Water Make-up solenoid
valve
Typical reservoir sight glass
Содержание BC-N4 Series
Страница 2: ......
Страница 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Страница 20: ...Page 20 THIS PAGE INTENTIONALLY BLANK ...
Страница 32: ...Page 32 THIS PAGE INTENTIONALLY BLANK ...
Страница 48: ...Page 48 THIS PAGE INTENTIONALLY BLANK ...
Страница 54: ...Page 54 THIS PAGE INTENTIONALLY BLANK ...
Страница 62: ...Page 62 THIS PAGE INTENTIONALLY BLANK ...
Страница 63: ...END 2016 ADVANTAGE ENGINEERING INC RE 09 27 2016 ...
Страница 64: ......