BC-N4 Glycol Chiller
Page: 28
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: [email protected]
3.
PRECAUTIONS:
The chiller control is programmed from the factory with a setpoint range of 48°
to 70°F. To operate below 48°F, the addition of inhibited propylene glycol and
modification of the limit control settings are required. Diligent monitoring of the
water/glycol solution is mandatory to prevent freezing of the evaporator. Freezing
may cause the evaporator to rupture allowing water and freon to mix which will
cause major damage to the refrigeration system.
R134A and R407C models operating above 70°F and R404A models operating
above 60°F require the addition of a refrigerant crankcase pressure regulating
(CPR) valve. The CPR valve is necessary to prevent overloading of the
compressor which can cause premature failure. R410A models may be operated
up to 80°F without a CPR valve.
Contact your local refrigeration contractor or the factory for further information.
The operating range of the chiller control may be changed to 10°F - 90°F by
adjusting the Setpoint Lockout (SPL) jumper. Refer to Section 3.3.c.3 of this
manual for more information.
B.
INSTRUMENT OPERATION
1.
To start the unit, toggle on the illuminated ON/OFF SWITCH. The pump will
start and the chiller control will begin temperature control operations.
2.
To select setpoint temperature, press and hold the UP ARROW or DOWN
ARROW keys until the desired set point temperature is displayed in the
TEMPERATURE WINDOW. The default range for the setpoint temperature is 48°
- 70°F or 9° - 21°C.
3.
The setpoint temperature can be displayed by pressing the UP ARROW or
DOWN ARROW keys. The setpoint temperature will be displayed for 5 seconds.
4.
When the compressor is turned off, the instrument will wait 3 minutes before
turning it back on regardless of the To Process temperature or setpoint. If a
fault has occurred, the control will attempt to turn the compressor back on after
3 minutes. If the fault condition remains, the compressor will not restart and
the control will retry after 1 minute. This sequence will repeat 3 times then the
system will lock-out and the unit must be powered off/on to restart the unit.
5.
Under normal conditions (no fault conditions, compressor has been off for
three minutes) the instrument will turn on the compressor when the To Process
temperature is above the setpoint. The instrument will engage the capacity
control system (digital unloading or hot gas bypass) when the To Process
temperature is below the setpoint by no more than 3 degrees.
Units equipped with a digital scroll compressor (M1D-5A, M1D-5W, M1D-
10A, M1D-10W, M1D-15A, M1D-15W) will operate in the unloaded state for a
maximum of 50 seconds out of every 60 seconds.
The instrument will turn off the compressor and capacity control system when the
To Process temperature is 4 degrees or more below the setpoint.
Содержание BC-N4 Series
Страница 2: ......
Страница 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Страница 20: ...Page 20 THIS PAGE INTENTIONALLY BLANK ...
Страница 32: ...Page 32 THIS PAGE INTENTIONALLY BLANK ...
Страница 48: ...Page 48 THIS PAGE INTENTIONALLY BLANK ...
Страница 54: ...Page 54 THIS PAGE INTENTIONALLY BLANK ...
Страница 62: ...Page 62 THIS PAGE INTENTIONALLY BLANK ...
Страница 63: ...END 2016 ADVANTAGE ENGINEERING INC RE 09 27 2016 ...
Страница 64: ......