IMPORTANT
These instructions, the layout drawing, local codes and ordinances, and applicable standards such as apply to
gas piping and electrical wiring comprise the basic information needed to complete the installation, and must
be thoroughly understood along with general building codes before proceeding.
Only personnel who have been trained and understand all applicable codes should undertake the installation.
Representatives that are Factory Certified in the service and application of this equipment and can be called on
for helpful suggestions about installation.
General information
GoGaS infrared heaters are manufactured in accordance with ANSI Z83.19-2009/CSA 2.35-2009. Each appliance
is subjected to a function test before it leaves the factory and is preset to the relevant gas type. For setting up and
operating radiation equipment, the following regulations and guidelines must be complied with.
This heater is approved for either indoor installation only. Not for use in residential dwellings, refer to rating
plate.
INSTALLATION CODES
The installation must conform with local building codes or, in the absence of local codes, with the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CSA B149.1.
GENERAL INSTALLATION AND GAS CODES/ELECTRICAL CODES
If an external electrical source is utilized, the heater, when installed, must be electrically grounded in accordance
with the National Electrical Code, ANSI/NFPA 70, or current Canadian Electrical Code, CSA C22.1.
AIRCRAFT HANGAR INSTALLATION
Installation in aircraft hangars must conform to the Standard for Aircraft Hangars, NSI/NFPA 409 in the US and
CAN/CGA B149.1 and B149.2 Installation Codes in Canada
PUBLIC GARAGES
Installation in public garages must conform to the Standard for Parking Structures, NFPA 88A or the Standard for
Repair Garages, NFPA 88B, in the US and CAN/CGA B149.1 and B149.2 Installation Codes in Canada.
PARKING STRUCTURES
Technical requirements are outlined in ANSI/NFPA 88A (USA)
Warning
Heaters should be installed so that the minimum clearances marked on the heater will be maintained from
vehicles parked below the heater.
INTRODUCTION
This appliance must be installed in accordance with current connection and installation regulations and may
only be used in adequately ventilated rooms. The installation and operating instructions must be inspected and
understood before installation and before start-up. Before installation it must be checked whether local gas
distributions, gas types and gas pressures as well as the settings of the appliance are compatible.