Page 7
High Efficiency - High Intensity
KMI_02142017al
INSTALLATION INSTRUCTIONS
•
Figures on the below illustrate the typical mounting configurations for the Series KMI heaters; verify which
is permissible by local codes.
•
Heaters must be hung at an angle between 0° and 30°. Typically, at the walls they are at 30° facing into the
building. The gas manifold must always be at the lower side of the heater.
•
Minimum ³/16" diameter 'S' hooks and No. 2/0 chain (200 lb./ 91 kg working load) is recommended. Close
'S' hooks after installation.
•
Never use a gas line as a hanging support and never locate gas or electric lines over the heaters.
•
Maintain clearance to combustibles.
•
Ensure that there is a plugged tap upstream of the heater or a fitting on the valve itself to verify incoming
pipeline pressure.
•
Do not leave the heater connected when pressure testing the pipeline. The high pressure will damage the
equipment.
High Intensity Mounting Instructions/Configurations
GoGaS High Intensity Heaters are approved to be operated horizontally and a maximum of 30° inclined angles (as
per figure below). Mounting kits are available and can be ordered separately. Use mounting points located on the
heater for installations.
Horizontally Mounted High Intensity Heater
Minimum Mounting Heights (horizontally) relative to Air Temperature
MODEL
NO.
CLEARANCES
(in)
RELATIVE TO AIR
TEMPERATURE
59° F
50° F
41° F
KMI 20
179 1/2
139 3/8
124 13/16
KMI 40
226 3/8
169 11/16 148 13/16
KMI 60
262 3/16
192 1/2
166 15/16
KMI 90
292 1/8
312 3/16 182 11/16
KMI 120
342 15/16
244 1/2
208 11/16
Mounting Hardware
BEAM CLAMP
SUSPENSION FOR
WOODEN MAIN BEAM
PIPE RING
OR CLEVIS