35
In Detail
DEVICE APPLICATIOn COnDITIOnS
Integrated device (VDE0160)
DIn En 50 178
General requirements
DIn En 60146-1-1:12.97
Design, vertical installation
Operating conditions
DIn En 60 146-1-1; ch. 2.5
Area of application, industrial
CISPR 6
Temperature behaviour
DIn En 60 146-1-1; ch. 2.2
Storage temperature (D)
-25 °C – +55 °C
Transport temperature (E)
-25 °C – +70 °C
Operating temperature (better B) -10 °C – +55 °C
humidity class
B
DIn En 50 178 Tab. 7 (En 60 721)
Degree of contamination
2
DIn En 50 178 Tab. 2
Air pressure
900 mbar * 1000 m above m. sea level
Index of protection
IP00
DIn En 69 529
Protection class
III
DIn En 50178 chap. 3
Mechanical jolt
DIn En 50 178 chap. 6.2.1
Tests in acc. with
DIn En 60 146-1-1 4.
EMC emitted interference
En 61000-6-4
Radio interference
suppression control unit
Class A
DIn En 55011:3.91 CISPR 11
EMC resistance
En 61000-6-2
ESD
8 kV (A)
En 61000-4-2:3.96
Burst control lines
1 kV (A)
En 61000-4-4
Conductor-bound
En 61000-4-6